Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: DENNIS STEEL INCORPORATED

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DENNIS STEEL INCORPORATED in 1105 LEANDER DRIVE, LEANDER, TX 78641 (NAICS 238120). OSHA activity number 339485401.

Watch Dennis Steel Incorporated — free Get an email when a new federal OSHA severe-injury report for Dennis Steel Incorporated is published. One employer, no account, unsubscribe in one click.
Site address
1105 LEANDER DRIVE
City
LEANDER
State
TX
ZIP
78641
Mailing
1105 LEANDER DRIVE, LEANDER, TX 78641
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238120
Employees
69
Ownership type
A

6 citations on file for this inspection.

1910.179 J03 IV

Serious Gravity 5 1 instance 60 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1680.00 Reduced
29 CFR 1910.179(j)(3)(iv): Deficiencies such as worn, cracked or distorted parts such as pins, bearings, shafts, gears, rollers, locking and clamping devices were not considered safety hazards:   On or about November 13, 2013, hooks used on overhead cranes through the facility and in the maintenance shop had missing or damaged safety latches, exposing employees to the hazard of being struck by a falling load.
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2800

1910.303 B02

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $1260.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about November 13, 2013, a surge protector was used to power a mini refrigerator, microwave, radio, an extension cord for power tools, and a light; which was not in accordance with instructions included in the listing or labeling, exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.303 F02

Serious Gravity 1 3 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  On or about July 23, 2012, each branch circuit in the breaker panel was not labeled to indicate its purpose, nor located and arranged so the purpose was evident:    a:  The branch circuits in breaker panel L3 were not labeled.  Panel L3 operates the 110 volt equipment in the facility.     b:  The branch circuits in breaker panel H3 were not labeled.  Panel H3 operates the 220 volt equipment in the facility.     c:  The 110 volt GE Powermark Plus breaker panel in the maintenance office was not labeled.  The panel powers the equipment in the maintenance office and shop.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 C04

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $1260.00 Reduced
29 CFR 1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface:  On or about November 13, 2013, a snap switch faceplate on the vehicle lift in the maintenance shop was missing a switch, exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.305 G01 IV A

Serious Gravity 1 2 instances 30 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  On or about November 13, 2013, flexible cords in the facility and maintenance office were used as permanent wiring, exposing employees to an electric shock hazard.           a:  An extension cord was used as permanent wiring to power a three-way splitter which, in turn, powered a toaster oven, microwave, mini refrigerator, and lamp.    b:  An extension cord was cut and used as permanent wiring to power a receptacle box in the maintenance shop to power a battery charging station.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 F06

Other-than-serious 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(f)(6): Except as provided in paragraphs (f)(7) and (f)(8) of this section, the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with either the information specified under paragraphs (f)(1)(i) through (v) of this section for labels on shipped containers or with the product identifier and pictures, symbols or combination thereof which provide at least general information regarding the hazards of the chemicals, and which, in conjunction with the other information immediately available  to employees under the hazard communication program, will provide employees with the specific information regarding the physical and health hazards of the hazardous chemical.    On or about November 13, 2013, employees used naphtha stored in a clear unmarked bottle, exposing employees to a fire and chemical hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339485401.