AUXVASSE, MO —
OSHA Inspection: FOSTER BROTHERS WOOD PRODUCTS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FOSTER BROTHERS WOOD PRODUCTS in 6465 HWY E, AUXVASSE, MO 65231 (NAICS 321999). OSHA activity number 339561300.
Where did this inspection happen?
- Establishment
- FOSTER BROTHERS WOOD PRODUCTS
- Site address
- 6465 HWY E
- City
- AUXVASSE
- State
- MO
- ZIP
- 65231
- Mailing
- P.O. BOX 232, AUXVASSE, MO 65231
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321999
- Employees
- 48
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.304 G05
- Issued
- Abate by
- Penalty
- Initial $2625.00 · Current $1838.00 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a. A shop light was used with a missing ground pin on the power cord. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $1837.5
- — Z (S) $2625
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a. In the shop, an extension cord was made with an outlet box; the box had a "knockout" missing from the side of the box (note: an outlet box designed for mounting is not listed for use as an extension cord). Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a. In the shop, 110 V receptacles were used with damaged or loose covers. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 A02 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service: a. The fabricated extension cord (with an outlet box as the receptacle) was used with a cover on the plug end, that was not in place (loose, potentially exposing terminal connections to the plug blades). (Note: there is no longer any approval for plugs with this type of cover, but must be of a solid construction.) Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 321999)
NORTH WILKESBORO, NC—2026-07-07
161501 - MILLER BEE SUPPLY, INC.
MIAMI, FL—2026-06-26
FLORIDA LUMBER COMPANY
PLATO, MN—2026-06-25
111471 - GREAT OAK EQUINE
PLATO, MN—2026-06-25
111470 - GREAT OAK EQUINE
DULUTH, MN—2026-06-23
111455 - NORTHSHORE WOOD PRODUCTS INC
More inspections in MO
KANSAS CITY, MO—2026-07-09