On , OSHA opened a referral safety inspection of FORMS AND SURFACES, INC. in 4318 BRYANT ROAD, ALLISON PARK, PA 15101 (NAICS 339950). OSHA activity number 339567240.

Watch Forms AND Surfaces, INC. — free Get an email when a new federal OSHA severe-injury report for Forms AND Surfaces, INC. is published. One employer, no account, unsubscribe in one click.
Site address
4318 BRYANT ROAD
City
ALLISON PARK
State
PA
ZIP
15101
Mailing
4318 BRYANT ROAD, ALLISON PARK, PA 15101
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
339950
Employees
37
Ownership type
A

5 citations on file for this inspection.

1910.242 B

Deleted Serious Gravity 1 2 instances 3 exposed
Issued
Penalty
Initial $1785.00 · Current $0.00 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:   (a) Facility, Compressed Air Nozzles: On or before January 30, 2014, employees used nozzles for cleaning workstations and parts with a regulated house air pressure measured above 30 psi.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1785

1910.303 B02

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $1785.00 · Current $1600.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:     (a) Facility, Manual Routing Table: On or before January 30, 2014, employees were exposed to fire and/or arcing part hazards in that a type NM-B cable clamp was used in lieu of a flexible cord connector at a metal utility box.
Recent events (2)
  • — I (O) $1600
  • — Z (S) $1785

1910.305 G01 IV A

Other-than-serious 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:     (a) Facility, Manual Table Router: On or before January 30, 2014, employees were exposed to fire and/or arcing part hazards in that a flexible power cord was being used in lieu of permanent wiring.        (b) Facility, Jet Turret Milling Machine: On or before January 30, 2014, employees were exposed to fire, arcing part, and/or tripping hazards in that a flexible power cord was being used in lieu of permanent wiring.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 A02 IX

Serious Gravity 1 1 instance 5 exposed
Issued
Penalty
Initial $1785.00 · Current $1600.00 Reduced
29 CFR 1910.305(a)(2)(ix): Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lamp holder with a guard:     (a) Facility, Routing Table Light: On or before January 30, 2014, employees were exposed to arcing part and/or electrical shock hazards in that the fluorescent light bulb was not protected from incidental contact.
Recent events (2)
  • — I (S) $1600
  • — Z (S) $1785

1910.212 A01

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:   (a) Facility, Jet Turret Milling Machine: On or before January 30, 2014, employees were exposed to machined material being ejected from the equipment.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0