Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ENRG1 LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ENRG1 LLC in 1738 ELMWOOD AVENUE, BUFFALO, NY 14207 (NAICS 236118). OSHA activity number 339580730.

Watch Enrg1 LLC — free Get an email when a new federal OSHA severe-injury report for Enrg1 LLC is published. One employer, no account, unsubscribe in one click.
Establishment
ENRG1 LLC
Site address
1738 ELMWOOD AVENUE
City
BUFFALO
State
NY
ZIP
14207
Mailing
391 WASHINGTON STREET, SUITE 800, BUFFALO, NY 14203
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236118
Employees
100
Ownership type
A

4 citations on file for this inspection.

1926.404 B01 I

Serious Gravity 1 1 instance 2 exposed
Issued
Penalty
Initial $1517.00 · Current $759.00 Reduced
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites:          a) On or about 2/10/14, in Banquet Room # 2, first floor, at the former FWS Furniture Store & Warehouse under renovation into apartments/commercial space, located at 1738 Elmwood Ave.,Buffalo, NY: A Triangle Engineering portable industrial fan was connected to 120 volt-ac power via a series of two extension cords, the first of which was a blue extension cord plugged into a receptacle of a 2- receptacle outlet box mounted on a column. No GFCI or assured equipment grounding program was being used.          NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $758.5
  • — Z (S) $1517

1926.404 F06

Serious Gravity 1 1 instance 2 exposed
Issued
Penalty
Initial $1517.00 · Current $759.00 Reduced
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:          a) On or about 2/10/14, in Banquet Room # 2, first floor, at the former FWS Furniture Store & Warehouse under renovation into apartments/commercial space, located at 1738 Elmwood Ave.,Buffalo, NY: A Triangle Engineering portable industrial fan was connected to 120 volt-ac power via a series of two extension cords, the first of which was a blue extension cord plugged into a receptacle of a 2- receptacle outlet box mounted on a column.  The plug on the power  cord of the fan lacked a ground prong.          NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $758.5
  • — Z (S) $1517

1926.20 B03

Serious Gravity 1 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.20(b)(3): Machinery, tool(s), material(s), or equipment which was not in compliance with the applicable requirement(s) of 29 CFR 1926 was not prohibited, and/or was not either identified as unsafe by tagging, or locking the controls to render them inoperable, or physically removed from its place of operation:     a) On or about 2/10/14, in Room # 229, second floor, at the former FWS Furniture Store & Warehouse under renovation into apartments/commercial space, located at 1738 Elmwood Ave.,Buffalo, NY: Although not connected to power at the time of the inspection, the plug on the power cord of a Marley Industrial Products portable fan lacked a ground prong. The fan was neither identified as unsafe by tagging, rendered inoperable, nor was it physically removed from the jobsite.     NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.416 E01

Other-than-serious 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables were used:     a) On or about 2/10/14, in Banquet Room # 2, first floor, at the former FWS Furniture Store & Warehouse under renovation into apartments/commercial space, located at 1738 Elmwood Ave.,Buffalo, NY: A Triangle Engineering portable industrial fan was connected to 120 volt-ac power via a series of two extension cords, the first of which was a blue extension cord plugged into a receptacle of a 2- receptacle outlet box mounted on a column. The outer sheath of the blue extension cord was badly frayed and crushed in spots, exposing the conductors.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339580730.