BINGHAMTON, NY —
OSHA Inspection: NELCORP ELECTRICAL CONTRACTING, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NELCORP ELECTRICAL CONTRACTING, INC. in BROOME CC, WALES ADMIN, 907 UPPER FRONT ST., BINGHAMTON, NY 13902 (NAICS 238210). OSHA activity number 339585739.
Where did this inspection happen?
- Establishment
- NELCORP ELECTRICAL CONTRACTING, INC.
- Site address
- BROOME CC, WALES ADMIN, 907 UPPER FRONT ST.
- City
- BINGHAMTON
- State
- NY
- ZIP
- 13902
- Mailing
- 2500 WATSON BOULEVARD, ENDWELL, NY 13760
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 2
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.403 B02
- Issued
- Penalty
- Initial $4620.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: a) North end of building, 1st floor corridor, on or about 2-13-14: Employees were using an energized box/cord assembly that was not being used in accordance with the manufacturers recommendations or as listed and labeled. b) North end of building, 1st floor corridor, on or about 2-13-14: Employees were obtaining power from a box assembly that had a makeshift extension to accommodate a thicker wall, not in accordance with the manufacturers recommendations or as listed and labeled.
Recent events (2)
- — I (S) $0
- — Z (S) $4620
1926.403 I02
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.403(i)(2): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures: a) North end of building, 1st floor corridor, on or about 2-13-14: Employees were working in the vicinity of an energized junction box with multiple extensions, open in several locations, with live parts visible and accessible. b) East side of building, entry/elevator area, on or about 2-13-14: Employees were working in the vicinity of a 12" x 12" open top energized junction box with live wires protruding, capped only with wire nuts. c) East side of building, entry/elevator area, on or about 2-13-14: Employees were working in the vicinity of an energized junction box with gaps between box extenders with live parts visible and accessible.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.405 B01
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed: a) North end of building, 1st floor corridor, on or about 2-13-14: Employees were using and working around an energized receptacle box that had a knockout missing.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.405 B02
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings were not provided with covers: a) North end of building, 1st floor corridor, on or about 2-13-14: Employees were working in the vicinity of an energized junction box with a damaged cover that was shimmed out well beyond the front of the box, with live parts visible and accessible. b) East side of building, entry/elevator area, on or about 2-13-14: Employees were working in the vicinity of a 12" x 12" open top energized junction box, without a cover. c) East side of building, entry/elevator area, on or about 2-13-14: Employees were working in the vicinity of an energized junction box with the cover and duplex receptacle disconnected from the box, with live parts visible and accessible.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.405 E01
- Issued
- Penalty
- Initial $3080.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1926.405(e)(1): In wet locations, cabinets, cutout boxes, fittings, boxes and panelboard enclosures were not weatherproof: a) East side of building, entry/elevator area, on or about 12-13-14: Employees were working in the vicinity of a 12" x 12" open top energized junction box, with water dripping in and around the box. b) East side of building, entry/elevator area, on or about 12-13-14: Employees were working in the vicinity of an energized junction box with the cover and duplex receptacle disconnected from the box, and water dripping in and around the box.
Recent events (2)
- — I (S) $0
- — Z (S) $3080
More inspections in this industry (NAICS 238210)
PARKVILLE, MD—2026-07-15
THE POWER SOURCE, INC.
SOUTH BARRINGTON, IL—2026-07-15
EDGE ELECTRICAL SYSTEMS, LLC
LAYTON, UT—2026-07-14
LYNN WOODWARD ELECTRIC LLC
BRIDGEPORT, WV—2026-07-14
INFINITY ELECTRIC & SERVICE COMPANY, LLC
ANNAPOLIS, MD—2026-07-14
J.M. MULLEN ELECTRICAL SERVICES, INC.
More inspections in NY
MAYVILLE, NY—2026-07-16
MAYVILLE VILLAGE DPW
NEW HYDE PARK, NY—2026-07-16
NORTH HEMPSTEAD TN MICHAEL J TULLY PARK
CONESUS, NY—2026-07-16
CONESUS TN HIGHWAY DEPT
COMSTOCK, NY—2026-07-15
NYSDOCCS WASHINGTON CORRECTIONAL FACILITY
BALDWINSVILLE, NY—2026-07-15
LYSANDER TOWN HIGHWAY DEPARTMENT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339585739.