OSHA Inspection: NELCORP ELECTRICAL CONTRACTING, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NELCORP ELECTRICAL CONTRACTING, INC. in BROOME CC, WALES ADMIN, 907 UPPER FRONT ST., BINGHAMTON, NY 13902 (NAICS 238210). OSHA activity number 339585739.

Watch Nelcorp Electrical Contracting, INC. — free Get an email when a new federal OSHA severe-injury report for Nelcorp Electrical Contracting, INC. is published. One employer, no account, unsubscribe in one click.
Site address
BROOME CC, WALES ADMIN, 907 UPPER FRONT ST.
City
BINGHAMTON
State
NY
ZIP
13902
Mailing
2500 WATSON BOULEVARD, ENDWELL, NY 13760
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

5 citations on file for this inspection.

1926.403 B02

Deleted Serious Gravity 5 2 instances 1 exposed
Issued
Penalty
Initial $4620.00 · Current $0.00 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) North end of building, 1st floor corridor, on or about 2-13-14:  Employees were using an energized box/cord assembly that was not being used in accordance with the manufacturers recommendations or as listed and labeled.     b) North end of building, 1st floor corridor, on or about 2-13-14:  Employees were obtaining power from a box assembly that had a makeshift extension to accommodate a thicker wall, not in accordance with the manufacturers recommendations or as listed and labeled.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4620

1926.403 I02

Deleted Serious Gravity 5 3 instances 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.403(i)(2): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures:    a) North end of building, 1st floor corridor, on or about 2-13-14:  Employees were working in the vicinity of an energized junction box with multiple extensions, open in several locations, with live parts visible and accessible.     b) East side of building, entry/elevator area, on or about 2-13-14:  Employees were working in the vicinity of a 12" x 12" open top energized junction box with live wires protruding, capped only with wire nuts.     c) East side of building, entry/elevator area, on or about 2-13-14:  Employees were working in the vicinity of an energized junction box with gaps between box extenders with live parts visible and accessible.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B01

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:    a) North end of building, 1st floor corridor, on or about 2-13-14:  Employees were using and working around an energized receptacle box that had a knockout missing.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B02

Deleted Serious Gravity 5 3 instances 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings were not provided with covers:    a) North end of building, 1st floor corridor, on or about 2-13-14:  Employees were working in the vicinity of an energized junction box with a damaged cover that was shimmed out well beyond the front of the box, with live parts visible and accessible.     b) East side of building, entry/elevator area, on or about 2-13-14:  Employees were working in the vicinity of a 12" x 12" open top energized junction box, without a cover.     c) East side of building, entry/elevator area, on or about 2-13-14:  Employees were working in the vicinity of an energized junction box with the cover and duplex receptacle disconnected from the box, with live parts visible and accessible.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 E01

Deleted Serious Gravity 5 2 instances 1 exposed
Issued
Penalty
Initial $3080.00 · Current $0.00 Reduced
29 CFR 1926.405(e)(1): In wet locations, cabinets, cutout boxes, fittings, boxes and panelboard enclosures were not weatherproof:    a) East side of building, entry/elevator area, on or about 12-13-14:  Employees were working in the vicinity of a 12" x 12" open top energized junction box, with water dripping in and around the box.     b) East side of building, entry/elevator area, on or about 12-13-14:  Employees were working in the vicinity of an energized junction box with the cover and duplex receptacle disconnected from the box, and water dripping in and around the box.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3080

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339585739.