BOSTON, MA —
OSHA Inspection: WADLEIGH & ASSOCIATES, INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of WADLEIGH & ASSOCIATES, INC in 190 WARREN AVENUE, BOSTON, MA 02115 (NAICS 236117). OSHA activity number 339608192.
Where did this inspection happen?
- Establishment
- WADLEIGH & ASSOCIATES, INC
- Site address
- 190 WARREN AVENUE
- City
- BOSTON
- State
- MA
- ZIP
- 02115
- Mailing
- 126 NORTH WASHINGTON STREET #5, BOSTON, MA 02114
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236117
- Employees
- 6
- Ownership type
- A
Citations
8 citations on file for this inspection.
1926.403 B02
- Issued
- Abate by
- Penalty
- Initial $1600.00 · Current $950.00 Reduced
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: Jobsite: Sitewide. Employees were exposed to electric shock and burns: a) while handling metal pre-punched knockout boxes where the boxes had not been mounted. b) Where the Romex branch circuit cables had not been adequately supported.
Recent events (2)
- — I (S) $950
- — Z (S) $1600
1926.405 A02 II B
- Issued
- Abate by
- Penalty
- Initial $1600.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(B): Temporary wiring branch circuits had been laid on the floor: Jobsite: First floor. Employees were exposed to electric shock and associated hazards where a branch circuit, which had been fashioned from non-metallic sheathed cable, had been laid on the corrugated metal decking.
Recent events (2)
- — I (S) $0
- — Z (S) $1600
1926.403 I02
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $550.00 Reduced
General-duty citation text
29 CFR 1926.403(i)(2): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures: Employees were exposed to electric shock where a lamp was missing from a socket on the temporary lighting stringer, exposing the live parts.
Recent events (2)
- — I (S) $550
- — Z (S) $1200
1926.405 A02 II E
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage: Jobsite: Parking garage. Employees were exposed to electric shock and burns while working around temporary lighting where two incandescent (2) lamps were not protected from breakage by protective cages.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.404 B01 II
- Issued
- Abate by
- Penalty
- Initial $1600.00 · Current $950.00 Reduced
General-duty citation text
29 CFR 1926.404(b)(1)(ii): All 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupers for personal protection: Jobsite: Parking garage and first floor. Employees were exposed to electric shock and associated hazards while using extension cords and utilization equipment where ground fault circuit interrupter had not been provided.
Recent events (2)
- — I (S) $950
- — Z (S) $1600
1926.404 F06
- Issued
- Penalty
- Initial $1600.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous: Jobsite: First floor. Employees were exposed to electric shock and associated hazards while using an extension cord with a missing grounding pin.
Recent events (2)
- — I (S) $0
- — Z (S) $1600
1926.405 B01
- Issued
- Abate by
- Penalty
- Initial $1600.00 · Current $950.00 Reduced
General-duty citation text
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed: Jobsite: First floor. Employees were exposed to electric shock and burns where there were several open knockouts, being as large as 2-1/4 inches, in the temporary service panel enclosure.
Recent events (2)
- — I (S) $950
- — Z (S) $1600
1926.405 G02 IV
- Issued
- Abate by
- Penalty
- Initial $1600.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws: Jobsite: Parking garage. Employees were exposed to electric shock and burns: a) while using an extension cord where the jacket at the female end was torn away, defeating the inherent strain relief and b) where a rubber cord was fed from the temporary power panel through an open knockout without using a connector.
Recent events (2)
- — I (S) $0
- — Z (S) $1600
More inspections in this industry (NAICS 236117)
NEWPORT BEACH, CA—2026-07-16
TRADEMARK CONSTRUCTION COMPANY, INC.
DOWNINGTOWN, PA—2026-07-09
NVR, INC.
WINSTON SALEM, NC—2026-07-08
161508 - CLAYTON PROPERTIES GROUP, INC.
PUNTA GORDA, FL—2026-07-08
SAGE HOMES LLC
LAKE STEVENS, WA—2026-07-02
WA317991942 - SEKISUI HOUSE WASHINGTON INC
More inspections in MA
BELLINGHAM, MA—2026-07-16
BELLINGHAM DEPARTMENT OF PUBLIC WORKS
PLYMOUTH, MA—2026-07-15
TECH-ETCH, INC.
WESTFIELD, MA—2026-07-15
BOISE CASCADE BUILDING MATERIALS DISTRIBUTION, L.L.C.
QUINCY, MA—2026-07-15
UNITEDWOR VM CONTRACTOR CORP
FALL RIVER, MA—2026-07-15
CRESCO LABS, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339608192.