Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WARTSILA DEFENSE, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of WARTSILA DEFENSE, INC. in 3617 KOPPENS WAY, CHESAPEAKE, VA 23323 (NAICS 336611). OSHA activity number 339653453.

Watch Wartsila Defense, INC. — free Get an email when a new federal OSHA severe-injury report for Wartsila Defense, INC. is published. One employer, no account, unsubscribe in one click.
Site address
3617 KOPPENS WAY
City
CHESAPEAKE
State
VA
ZIP
23323
Mailing
3617 KOPPENS WAY, CHESAPEAKE, VA 23323
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336611
Employees
65
Ownership type
A

4 citations on file for this inspection.

1910.106 D03 I

Other-than-serious 1 instance 10 exposed
Issued
Penalty
Initial $2295.00 · Current $1721.00 Reduced
29 CFR 1910.106(d)(3)(i): More than 60 gallons of Category 1, 2, or 3 flammable liquids were stored in a storage cabinet.    a.)  Wartsila Defense, Inc., Propeller Shop:  On or about 03/26/14, the employer had more than 60 gallons of Category 1, 2, or 3 flammable liquids stored in a flammable storage cabinet.
Recent events (2)
  • — I (O) $1721
  • — Z (S) $2295

1910.106 E06 II

Other-than-serious 2 instances 10 exposed
Issued
Penalty
Initial $2295.00 · Current $1721.00 Reduced
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected.    a.)  Wartsila Defense, Inc., Propeller Shop:  On or about 03/26/14, employees were dispensing from a 55 gallon drum of acetone which was a category 2 flammable liquid with a flashpoint of 0 degrees Fahrenheit, into a container without the nozzle and container being electrically interconnected.    b.)  Wartsila Defense, Inc., Propeller Shop:  On or about 03/26/14, employees were dispensing from a 55 gallon drum of methanol which was a category 2 flammable liquid with a flashpoint of 50 degrees Fahrenheit, into a container without the nozzle and container being electrically interconnected.
Recent events (2)
  • — I (O) $1721
  • — Z (S) $2295

1910.212 B

Other-than-serious 1 instance 5 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving:  a.)  Wartsila Defense, Inc., Center Bay:  On or about 04/01/14, the Porter Cable drill press was not anchored to prevent walking or moving.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.304 F01 VIII

Other-than-serious 1 instance 20 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD."  a.)  Wartsila Defense, Inc., Center Bay, Panel Boxes LM-1 and LM-2:  On or about 04/01/14, employees were using the non-SWD breakers in the panel boxes to turn the fluorescent lights in the bay on and off on a daily basis.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View WARTSILA DEFENSE, INC.'s full OSHA safety record →