BULLARD, TX —
OSHA Inspection: EAST TEXAS UTILITY SERVICES INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of EAST TEXAS UTILITY SERVICES INC. in 3967 FM 2493 E, BULLARD, TX 75757 (NAICS 238210). OSHA activity number 339662462.
Where did this inspection happen?
- Establishment
- EAST TEXAS UTILITY SERVICES INC.
- Site address
- 3967 FM 2493 E
- City
- BULLARD
- State
- TX
- ZIP
- 75757
- Mailing
- 8250 FM 347 SOUTH, JACKSONVILLE, TX 75766
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 17
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.453 B02 V
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $900.00 Reduced
General-duty citation text
29 CFR 1926.453(b)(2)(v): A body belt was worn and a lanyard attached to the boom or basket when working from an aerial lift: The employer did not ensure that an employee working from aerial lift was protected from fall hazards. This violation occurred on or about April 2, 2014 at a jobsite located at 3967 FM 2493 E, Bullard, TX 75757; where an employee who was working from a truck-mounted aerial lift was not wearing a body harness with a lanyard attached to the boom or basket, although the harnesses and lanyards were available at the job site.
Recent events (2)
- — I (S) $900
- — Z (S) $2800
1926.950 C01
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $4000.00 Reduced
General-duty citation text
29 CFR 1926.950(c)(1): An employee was permitted to approach or take a conductive object without an approved insulating handle closer to exposed energized parts than shown in Table V-1: The employer did not ensure that an employee maintained the minimum working distance from energized overhead power lines. This violation occurred on or about April 2, 2014, at a jobsite located at 3967 FM 2493 East, Bullard, Texas 75757; where at least one employee, who was working from an aerial lift, approached an energized 14.4 kV overhead power line closer than 2-feet without insulated gloves, sleeves, and guarding equipment which were available at the job site.
Recent events (2)
- — I (S) $4000
- — Z (S) $7000
More inspections in this industry (NAICS 238210)
PARKVILLE, MD—2026-07-15
THE POWER SOURCE, INC.
SOUTH BARRINGTON, IL—2026-07-15
EDGE ELECTRICAL SYSTEMS, LLC
LAYTON, UT—2026-07-14
LYNN WOODWARD ELECTRIC LLC
BRIDGEPORT, WV—2026-07-14
INFINITY ELECTRIC & SERVICE COMPANY, LLC
ANNAPOLIS, MD—2026-07-14
J.M. MULLEN ELECTRICAL SERVICES, INC.
More inspections in TX
WICHITA FALLS, TX—2026-07-16
UNITED RENTALS, INC.
SAN MARCOS, TX—2026-07-16
CASA MECHANICAL SERVICES, LTD.
CLARKSVILLE, TX—2026-07-15
SEQUOIAS TREE EXPERT LLC
EL PASO, TX—2026-07-15
SURE STEEL
CORPUS CHRISTI, TX—2026-07-15
NORTH STAR ENERGY SOLUTIONS LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339662462.