TECUMSEH, OK —
OSHA Inspection: LONGREACH STEEL INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of LONGREACH STEEL INC in 38174 HWY 9, TECUMSEH, OK 74873 (NAICS 332322). OSHA activity number 339740128.
Where did this inspection happen?
- Establishment
- LONGREACH STEEL INC
- Site address
- 38174 HWY 9
- City
- TECUMSEH
- State
- OK
- ZIP
- 74873
- Mailing
- PO BOX 195, TECUMSEH, OK 74873
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332322
- Employees
- 6
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.305 A02 I
- Issued
- Penalty
- Initial $2000.00 · Current $1200.00 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installation(s) 600 volts, nominal, or less were used in prohibited manners:Note: Temporary electrical power and lighting installation(s) may only be used as specified by 1910.305(a)(2)(i)(A) through 1910.305(a)(2)(i)(C). Trim Shop. On or about April 23, 2014 and at times prior thereto, temporary electrical wiring was used to provide power to the Kentex Trim Slitter and employees were exposed to electrical shock.
Recent events (2)
- — I (S) $1200
- — Z (S) $2000
1910.305 B01 II
- Issued
- Penalty
- Initial $1600.00 · Current $960.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Trim Shop. On or about April 23, 2014 and at times prior thereto, several open knockouts in the breaker box were not effectively closed or covered and employees were exposed to electrical shock.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
More inspections in this industry (NAICS 332322)
CASTLE ROCK, CO—2026-07-10
MASTER MAGNETICS, INC.
PITTSBURG, KS—2026-07-09
PROGRESSIVE PRODUCTS INC
NEW ROCHELLE, NY—2026-07-09
HEFTI HARBOR ELEC FAB & TOOLS
LAKEWOOD, WA—2026-07-08
WA317992020 - KRUEGER SHEET METAL CO
SOUTHAMPTON, MA—2026-07-07
LYMAN SHEET METAL CO., INC
More inspections in OK
MADILL, OK—2026-07-08
MID AMERICAN STEEL & WIRE CO., LLC
SEILING, OK—2026-06-26
GORE ENERGY
ADA, OK—2026-06-25
PAN AMERICA ELECTRIC , INC.
ADA, OK—2026-06-25
CITATION OIL & GAS CORPORATION
EDMOND, OK—2026-06-23
BRICK EXPERTS INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339740128.