NEW HAVEN, CT —
OSHA Inspection: NEW HAVEN RESIDUALS, LP
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of NEW HAVEN RESIDUALS, LP in 345 EAST SHORE PARKWAY, NEW HAVEN, CT 06512 (NAICS 811310). OSHA activity number 339864027.
Where did this inspection happen?
- Establishment
- NEW HAVEN RESIDUALS, LP
- Site address
- 345 EAST SHORE PARKWAY
- City
- NEW HAVEN
- State
- CT
- ZIP
- 06512
- Mailing
- 435 WILLIAMS COURT SUITE 100, BALTIMORE, MD 21220
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811310
- Employees
- 13
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.147 C04 I
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $1500.00 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: ESTABLISHMENT: The employer did not develop a complete energy control procedure for controlling of hazardous energy when employees were required to perform maintenance and/or repair of machines, such as hydraulic lines leading to the cylinder driving the Influent valve, in that the LOTO permit did not include as a step the bleeding or checking of the bleeding of pressure from the hydraulic lines.
Recent events (2)
- — I (O) $1500
- — Z (S) $4500
1910.37 A04
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: INLET WORK BUILDING: The emergency exit sign was not lit as required.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.146 C09 I
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.146(c)(9)(i): Each contractor who was retained to perform permit space entry operations did not obtain any available information regarding permit space hazards and entry operations from the host employer: ESTABLISHMENT: The contractor retained to perform maintenance and/or repair of waste water pump stations where permit required confined spaces were present, did not obtain any available information regarding permit space hazards and entry operations from the host employer.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 811310)
CHRISTIANSBURG, VA—2026-07-09
BGIS GLOBAL INTEGRATED SOLUTION US, LLC
SEATTLE, WA—2026-07-09
WA317992010 - FLAGSHIP MANAGEMENT LLC
STATESBORO, GA—2026-07-08
TAYLOR BUILT PRODUCTS
, AK—2026-07-08
ANGUS ENTERPRISES
LOS ANGELES, CA—2026-07-08
CHILLEST INDUSTRIES LLC
More inspections in CT
ENFIELD, CT—2026-07-16
MOMS ENFIELD
DAYVILLE, CT—2026-07-16
HARBOR FREIGHT
NEW BRITAIN, CT—2026-07-14
JANANII, LLC
NEWINGTON, CT—2026-07-14
TRUSS MANUFACTURING INC
NORTH BRANFORD, CT—2026-07-14
NYK STATEWIDE MOLINA CONSTRUCTION LLC
Source