OSHA Inspection: DEPARTMENT OF PUBLIC WORKS NAVAL BASE VENTURA COUNTY NAVFAC SOUTHWEST

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of DEPARTMENT OF PUBLIC WORKS NAVAL BASE VENTURA COUNTY NAVFAC SOUTHWEST in MUGU RD BUILDING 211, POINT MUGU NAWC, CA 93042 (NAICS 928110). OSHA activity number 339869455.

Watch Department OF Public Works Naval Base Ventura County Navfac Southwest — free Get an email when a new federal OSHA severe-injury report for Department OF Public Works Naval Base Ventura County Navfac Southwest is published. One employer, no account, unsubscribe in one click.
Site address
MUGU RD BUILDING 211
City
POINT MUGU NAWC
State
CA
ZIP
93042
Mailing
311 MAIN ROAD BLDG 66, POINT MUGU NAWC, CA 93042
Inspection type
Unprogrammed Related (G)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
10
Ownership type
D

2 citations on file for this inspection.

1910.269 A03

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(a)(3): The employer did not determine existing conditions related to the safety of the work to be performed before work on or near electric lines or equipment was started:   On or about 13 June 2014, Naval Base Point Mugu's Department of Public Works failed to confirm that the A3-T211 is a 150KVA 4160-120/208V 3 Phase delta/wye dry pack transformer was free of corrosive residue. Corrosive foreign material residue was present where internal fuses make contact on the lower bus, exposing employees to flash arc, electrical shock and electrocution hazards.
Recent events (1)
  • — Z (S) $0

1910.269 D06 IV

Serious Gravity 10 2 instances 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(d)(6)(iv): Lockout or tag out devices were not affixed to each energy isolating device by authorized employees:  On or about 13 June 2014 the Employer failed to ensure that lock out or tag out devices were used in order to secure the primary side of A3-T211 transformer with either a 5 point head screw needing a specialized tool, or a tag to ensure high side is not accessible by unauthorized personnel in which an employee made contact with a closed circuit.