BINGHAMTON, NY —
OSHA Inspection: PEPSI BEVERAGES COMPANY, NORTHEAST UPSTATE DIVISION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PEPSI BEVERAGES COMPANY, NORTHEAST UPSTATE DIVISION in 5 BROAD AVENUE, BINGHAMTON, NY 13904 (NAICS 424490). OSHA activity number 339888935.
Where did this inspection happen?
- Establishment
- PEPSI BEVERAGES COMPANY, NORTHEAST UPSTATE DIVISION
- Site address
- 5 BROAD AVENUE
- City
- BINGHAMTON
- State
- NY
- ZIP
- 13904
- Mailing
- 5 BROAD AVENUE, BINGHAMTON, NY 13904
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424490
- Employees
- 65
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.253 B04 III
- Issued
- Penalty
- Initial $2380.00 · Current $1666.00 Reduced
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: a) Maintenance, on or about 8/7/14: Oxygen and acetylene gas cylinders were stored together.
Recent events (2)
- — I (S) $1666
- — Z (S) $2380
1910.304 G05
- Issued
- Penalty
- Initial $2380.00 · Current $1666.00 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) Fleet Shop, on or about 8/6/14: Extension cord used to charge electric pallet jacks was not provided with a continuous and effective path to ground in that the ground pin was missing from the plug. b) At the facility, on or about 8/6/14: Crown pallet jack, Model WP 2330-45, was not provided with a continuous and effective path to ground in that the ground pin was missing from the plug connector.
Recent events (2)
- — I (S) $1666
- — Z (S) $2380
More inspections in this industry (NAICS 424490)
WAUWATOSA, WI—2026-07-09
SPARTAN NASH COMPANY
BEAVERTON, OR—2026-07-07
317744718 - THE ICEE CO
WINONA, MN—2026-07-07
111537 - WATER SYSTEMS COMPANY
DOVER FOXCROFT, ME—2026-07-06
SHAW'S SUPERMARKETS
REDDING, CA—2026-06-24
THE AMERICAN BOTTLING GROUP
More inspections in NY
POUGHKEEPSIE, NY—2026-07-13
MARCO BOARD HOUSE, INC.