1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: PMP, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PMP, LLC in 879 WASHINGTON STREET, SAINT MARYS, PA 15857 (NAICS 332117). OSHA activity number 340039148.

Watch PMP, LLC — free Get an email when a new federal OSHA severe-injury report for PMP, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
PMP, LLC
Site address
879 WASHINGTON STREET
City
SAINT MARYS
State
PA
ZIP
15857
Mailing
879 WASHINGTON STREET, SAINT MARYS, PA 15857
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332117
Employees
63
Ownership type
A

4 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $3000.00 Reduced
OSH ACT of 1970 Section (5)(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees:   A.)  PMP LLC dba Metal Powder Products Company - On or about 10/22/14, Employees were exposed to struck by hazards from lifting devices not being load rated and/or marked with load capacity.  Drum latches used to lift drums weighing 600 pounds with hoists were not load tested and/or marked with lifting capacity.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1910.303 B02

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $3400.00 · Current $2550.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    A.)  PMP LLC, dba Metal Powder Products Company - On or about 10/22/14, employees were utilizing household type fans for activities including but not limited to, drying oil off of parts.  The fans were not designed for use in industrial environments.
Recent events (2)
  • — I (S) $2550
  • — Z (S) $3400

1910.303 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $3000.00 Reduced
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided:  A.)  PMP, LLC dba Metal Powder Products Company/back press department  - The covers for the receptacle outlet boxes installed in the presses were missing and/or had been removed.  The condition allowed for the receptacle outlets to be exposed to oil from the presses.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1910.334 A01

Other-than-serious 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(a)(1): Flexible electric cords were otherwise hung in such a fashion as could damage the outer jacket or insulation:    A,)  PMP LLC dba Metal Powder Products Inc. - On or about 10/22/14, extension cords were being wrapped around the metal stand of a conveying machine.  The cord was being used to power the conveying equipment.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

PMP, LLC

PMP, LLC

PMP, LLC

PMP, LLC

View PMP, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340039148.