Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: POLYMER DYNAMIX, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of POLYMER DYNAMIX, LLC in 238 ST. NICHOLAS AVE., SOUTH PLAINFIELD, NJ 07080 (NAICS 325211). OSHA activity number 340101245.

Watch Polymer Dynamix, LLC — free Get an email when a new federal OSHA severe-injury report for Polymer Dynamix, LLC is published. One employer, no account, unsubscribe in one click.
Site address
238 ST. NICHOLAS AVE.
City
SOUTH PLAINFIELD
State
NJ
ZIP
07080
Mailing
238 ST. NICHOLAS AVE., SOUTH PLAINFIELD, NJ 07080
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325211
Employees
17
Ownership type
A

3 citations on file for this inspection.

1910.305 A02 I

Serious Gravity 5 1 instance 17 exposed
Issued
Penalty
Initial $2000.00 · Current $2000.00
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installations of 600 volts, nominal, or less were used for purposes other than those permitted in subparagraphs (a), (b) and (c) of this paragraph 1910.305(a).  Temporary wiring was used for permanent use:  a- Polymer Dynamix, LLC, South Plainfield, NJ, Manufacturing Area, mezzanine level - Extension cords were used to power machinery that is used on a regular basis in lieu of permanent wiring.  1- Mezzanine level - Ridgid vacuum cleaner  Condition noted on or about 11/21/14.
Recent events (1)
  • — Z (S) $2000

1910.307 C01

Serious Gravity 10 1 instance 17 exposed
Issued
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1910.307(c)(1):  Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe or approved for the hazardous (classified) location, or safe for the hazardous (classified) location:    a- Polymer Dynamix, LLC, South Plainfield, NJ - Manufacturing/Plant Areas:      - Micro Air RP-8 Dust Collector     - 25 mm, 50mm and 58mm Extruder Machines     - regular vacuum cleaners  Means were not provided to prevent a fire/explosion hazard, in that, the machinery/equipment and/or wiring used in the Class II combustible locations were not approved for the Class II, Division II locations.  Condition noted on or about 11/21/14.  REFERENCE:  NFPA 70E STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE - ARTICLES 500 & 502  29 CFR 1910.307 OSHA GENERAL INDUSTRY CODE OF REGULATIONS  NFPA 499 CLASSIFICATION OF COMBUSTIBLE DUSTS AND OF HAZARDOUS (CLASSIFIED) LOCATIONS FOR ELECTRICAL INSTALLATIONS IN CHEMICAL PROCESS AREAS, 2013 EDITION - CHAPTER 5, SECTION 5.1.  NFPA 654 STANDARD FOR THE PREVENTION OF FIRE AND DUST EXPLOSIONS FROM THE MANUFACTURING, PROCESSING, AND HANDLING OF COMBUSTIBLE PARTICULATE SOLIDS, 2013 EDITION, CHAPTER 6, SECTION 6.5.2
Recent events (1)
  • — Z (S) $2800

1910.1200 H03 IV

Other-than-serious 1 instance 17 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(h)(3)(iv): The details of the hazard communication program developed by the employer, did not include an explanation on the safety data sheet, including the order of information and how employees can obtain and use the appropriate hazard information:  a- Polymer Dynamix, LLC, South Plainfield, NJ - Employee training on the new label elements and the safety data sheet (SDS) format for the revised hazard communication standard (HCS) was not conducted.  Condition noted on or about 11/21/14.
Recent events (1)
  • — Z (O) $0

View POLYMER DYNAMIX, LLC's full OSHA safety record →