Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: SAVANNA ENERGY SERVICES CORPORATION RIG 632

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SAVANNA ENERGY SERVICES CORPORATION RIG 632 in RANCH ROAD 2469, MERTZON, TX 76941 (NAICS 213111). OSHA activity number 340137397.

Watch Savanna Energy Services Corporation RIG 632 — free Get an email when a new federal OSHA severe-injury report for Savanna Energy Services Corporation RIG 632 is published. One employer, no account, unsubscribe in one click.
Site address
RANCH ROAD 2469
City
MERTZON
State
TX
ZIP
76941
Mailing
2445 TECHNOLOGY FOREST BLVD SUITE 200, THE WOODLANDS, TX 77381
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213111
Employees
22
Ownership type
A

3 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 1 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1800.00 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:   On or about December 12, 2014 and in times prior thereto a breaker slot was not covered, exposing employees to the hazards of electrical shock, located in the 120/240 Volt breaker panel feeding the company trailer house.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

1910.305 G02 III

Serious Gravity 1 2 instances 22 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1800.00 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.  On or about December 12, 2014 and in times prior thereto, strain relief on 480 volt electrical cords' plugs was not provided, exposing employees to the hazards of electrical shock and fire:  a:  Power cord to dog house, located on main electrical distribution trailer. b.  Power cord to transformer, located near the company trailer.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

1910.307 C01

Serious Gravity 1 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1800.00 Reduced
29 CFR 1910.307(c)(1): Equipment and associated wiring was not approved as intrinsically safe when used in any hazardous (classified) location:  On or about December 12, 2014, located under the mud tanks, where subject to ignitable vapors, the wrong covers were used on Cooper explosion proof switches.  As a result, the screws used to attach the covers did not fit and were missing, exposing employees to the hazards of fire and explosion.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340137397.