OSHA Inspection: POSIES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of POSIES, INC. in 219 NORTH DUKE STREET, HUMMELSTOWN, PA 17036 (NAICS 811111). OSHA activity number 340148501.

Watch Posies, INC. — free Get an email when a new federal OSHA severe-injury report for Posies, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
POSIES, INC.
Site address
219 NORTH DUKE STREET
City
HUMMELSTOWN
State
PA
ZIP
17036
Mailing
219 NORTH DUKE STREET, HUMMELSTOWN, PA 17036
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811111
Employees
7
Ownership type
A

7 citations on file for this inspection.

1910.106 E02 II

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.106(e)(2)(ii): Flammable liquids were not stored in tanks or closed containers:  a) PAINT PREP ROOM: On or about December 19, 2014 an open plastic container of "lacquer thinner" was stored on the work bench. The open container allowed the flammable vapors to vent into the room.  Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $0

1910.107 C06

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for     Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations:  a)  SPRAY AREA: The area located outside of the spray booth but still within the spray room was not provided with illumination that is approved for a class 1 location. On or about December 19, 2014 several "open" faced fluorescent light fixtures were mounted on the ceiling and wall within 20 feet of the spray booth and without a separating partition.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $0

1910.107 C07

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.107(c)(7): Electric lamps outside of but within 20 feet of spraying area(s), and not separated therefrom by partition(s), were not totally enclosed to prevent the falling of hot particles, and were not protected from mechanical injury by suitable guards or location:  a)  SPRAY AREA: The area located outside of the spray booth but still within the spray room was not provided with illumination that is approved for a class 1 location. On or about December 19, 2014 several "open" faced fluorescent light fixtures were mounted on the ceiling and wall within 20 feet of the spray booth and without a separating partition.   these fixtures were immediately adjacent and above spraying operations.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $0

1910.252 A02 III A

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.252(a)(2)(iii)(A): The employer did not provide fire watchers whenever welding or cutting was performed in locations where other than a minor fire might develop.  a) SHOP FLOOR: No fire watch is utilized when welding and cutting is performed within a structure known to contain combustible materials including building components and flammable liquids such as gasoline found in tanks of cars on or about December 19, 2014.  Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listed or labeling:  a)  DETAILING AREA: A receptacle box, designed for a fixed installation, was wired to an orange flexible cord an lain across the floor area on or about December 19, 2014.  There was no face plate on the box.  Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $0

1910.334 A02 II

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service and an employee was using it before repairs and tests necessary to render the equipment safe were made:  a)  DETAILING AREA: A receptacle box, designed for a fixed installation, was wired to an orange flexible cord an lain across the floor area on or about December 19, 2014.  There was no face plate on the electrical box.  Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $0

1910.303 G01

Other-than-serious 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  a)  SHOP AREA - The employer did not ensure that the space in front of two adjacent electrical panels on the shop floor had ready and safe access to the panel, in that access to the panels was hindered by a shelving system and charging components, thereby exposing employees to possible injuries, on or about December 19, 2015.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (O) $0