Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: HOG INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of HOG INC in RR 2 BOX 8, GREENFIELD, IL 62044 (NAICS 493130). OSHA activity number 340161983.

Watch HOG INC — free Get an email when a new federal OSHA severe-injury report for HOG INC is published. One employer, no account, unsubscribe in one click.
Establishment
HOG INC
Site address
RR 2 BOX 8
City
GREENFIELD
State
IL
ZIP
62044
Mailing
RR 2 BOX 8, GREENFIELD, IL 62044
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493130
Employees
14
Ownership type
A

4 citations on file for this inspection.

1910.132 A

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $1700.00 · Current $1020.00 Reduced
29 CFR 1910.132(a): Protective equipment was not maintained in a sanitary and reliable condition:       The company did not provide reliable protective equipment for fall protection due to the use of expired DB Sala Layard Model Number 1201106, and the non-approved use of a Guardian Harnesses with the DB Sala Lanyard.    Employees were exposed to fall over 25 feet from a lower level while conducting service work on legs of the facility.
Recent events (2)
  • — I (S) $1020
  • — Z (S) $1700

1910.303 E01 I

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $1020.00 · Current $612.00 Reduced
29 CFR 1910.303(e)(1)(i):  Electric equipment shall not be used unless markings have been placed on equipment such as the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product may be identified:       An electrical box in the milling room did not have markings to identify manufacturers name, trademark, or other descriptive markings.  The employees working in the milling room are exposed to possible combustible dust hazards from grain legs feeding processing equipment.
Recent events (2)
  • — I (S) $612
  • — Z (S) $1020

1910.303 E01 II

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(e)(1)(ii):  Electric equipment shall not be used unless markings have been placed on equipment such as voltage, current, wattage and other ratings as necessary:    An electrical box used in the milling room did not have markings giving voltage, current, wattage, or other ratings such as classification ratings for hazardous locations.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.307 C02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $1700.00 · Current $1020.00 Reduced
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present:    An electrical box used to service lighting in the mill room was not approved for the ignitable or combustible properties of grain dust that could be present in the room.
Recent events (2)
  • — I (S) $1020
  • — Z (S) $1700

HOG INC

HOG INC

View HOG INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340161983.