Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: EAST COAST CHEVY, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of EAST COAST CHEVY, INC. in 4154A SKYRON DRIVE, DOYLESTOWN, PA 18902 (NAICS 441310). OSHA activity number 340166495.

Watch East Coast Chevy, INC. — free Get an email when a new federal OSHA severe-injury report for East Coast Chevy, INC. is published. One employer, no account, unsubscribe in one click.
Site address
4154A SKYRON DRIVE
City
DOYLESTOWN
State
PA
ZIP
18902
Mailing
4154A SKYRON DRIVE, DOYLESTOWN, PA 18902
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441310
Employees
14
Ownership type
A

11 citations on file for this inspection.

1910.23 C01

Serious Gravity 5 2 instances 9 exposed
Issued
Abate by
Penalty
Initial $2400.00 · Current $1800.00 Reduced
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:  a)  Metal Fabrication Area - On or about January 7, 2015, a standard railing was not provided on the open sides of the second story parts storage area to prevent employees from falling to the lower level.  b)  Shipping Receiving Area - On or about January 7, 2015, a standard railing was not provided on the open sides of the second story loading area and box storage area to prevent employees from falling to the lower level.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $2400

1910.24 H

Serious Gravity 5 2 instances 9 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1500.00 Reduced
29 CFR 1910.24(h): Standard railings were not provided on the open sides of all exposed stairways and stair platforms:  a)  Metal Fabrication Area - On or about January 7, 2015, the stairway leading to the mezzanine area was not provided with a standard guardrail on the open sides of the steps and does not extend to full length of stairway to the top riser.  b)  Shipping and Receiving Area - On or about January 7, 2015, the stairway leading to the mezzanine area was not provided with a standard guardrail on the open sides of the steps.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2000

1910.303 B02

Serious Gravity 1 3 instances 9 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $900.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:          a)  Shipping and Receiving - On or about January 7, 2015, a relocatable power tap is being used as an alternative to fixed wiring at work bench.  b)  Welding Shop - On or about January 7, 2015, a relocatable power tap is being used as a permanenent power source to power a grinder and other equipment.  c)  Mechanical Shop - On or about January 7, 2015, a relocatable power tap is being used as an alternative to fixed wiring.
Recent events (2)
  • — I (S) $900
  • — Z (S) $1200

1910.305 G02 III

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $900.00 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  a)  Mechanical Shop - On or about January 7, 2015, the electrical cord used to power the portable shop light is not provided with a tension relief device which split the exterior insulation at the joint, exposing the internal wiring.
Recent events (2)
  • — I (S) $900
  • — Z (S) $1200

1910.305 G01 IV A

Serious Gravity 1 3 instances 5 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $900.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure  a)  Shipping / Receiving - On or about January 7, 2015, flexible cords attached to outlets at the overhead mezzanine were attached over the door frame and routed to a workbench at the lower level.
Recent events (2)
  • — I (S) $900
  • — Z (S) $1200

1910.305 G01 IV D

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces:  a)  Shipping and Receiving - On or about January 7, 2015, flexible cords attached to outlets at the overhead mezzanine were attached over the door frame and routed to a workbench at the lower level.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A02 II

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $1200.00 Reduced
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service:  a)  Welding Shop - On or about January 7, 2015, the flexible wiring powering the Daytona Bench Grinder has damaged outer sheathing which has been improperly repaired and has not been taken out of service.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $1600

1910.1200 E01

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $900.00 Reduced
29 CFR 1910.1200(e)(1): Employer had not developed or implemented a written hazard communication program included the requirements outlined in 29 CFR 1910.1200(e)(1)(i) and (e)(1)(ii):   a)  Worksite - On or about January 7, 2015, the employer did not develop a written Hazard Communication program for the chemicals used in the workplace.
Recent events (2)
  • — I (S) $900
  • — Z (S) $1200

1910.1200 G08

Serious Gravity 1 2 instances 9 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(g)(8): The employer did not maintain copies of the required material safety data sheets for each hazardous chemical in the workplace:  a)  Mechanical Shop - On or about January 7, 2015, the employer did not provided Material Safety Data Sheets for the chemicals employees are using to clean engine parts.  b)  Welding Shop - On or about January 7, 2015, the employer did not provided with Material Safety Data Sheets for the employee who performs welding on sheet metal and uses other types of chemicals.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 H01

Serious Gravity 1 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area:  a)  Shop wide - On or about January 7, 2015, the employer did not provide employees with training on the hazards of chemicals used in the workplace.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.178 L06

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l):  a)  Shipping and Receiving Area - On or about January 7, 2015, the employer did not certify that each operator was evaluated prior to operating a forklift.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340166495.