Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WINDSOR QUALITY FOODS

Unprogrammed Related inspection · Health discipline

On , OSHA opened an unprogrammed Related health inspection of WINDSOR QUALITY FOODS in 601 EAST 3RD STREET, LAMPASAS, TX 76550 (NAICS 311412). OSHA activity number 340210582.

Watch Windsor Quality Foods — free Get an email when a new federal OSHA severe-injury report for Windsor Quality Foods is published. One employer, no account, unsubscribe in one click.
Site address
601 EAST 3RD STREET
City
LAMPASAS
State
TX
ZIP
76550
Mailing
3355 W. ALABAMA ST. #730, HOUSTON, TX 77098
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311412
Employees
391
Ownership type
A

4 citations on file for this inspection.

1910.37 A03

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $3000.00

Hazardous substances 14101560

29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    On or about January 23, 2015, in the raw materials receiving bay near the battery charging station, the aisle to the dock exit door was blocked by pallet(s) containing cardboard bales, exposing employees to the hazards of fire.
Recent events (2)
  • — I (O) $3000
  • — Z (S) $3000

1910.151 C

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $5000.00

Hazardous substances 2140S227

29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:    On or about January 23, 2015, in the chemical cage, where highly corrosive chemicals including, but not limited to, Enviro Klor HD (pH 14.0) were dispensed from drums and totes into open pails by contract employee(s), facilities for quick drenching or flushing of the eyes and body were not accessible for immediate emergency use within the work area. Travel around spill containment pallets for drums/totes and the long gate was required to reach the eye wash outside the chemical cage, and the nearest emergency shower/eyewash was located more than 50 feet away in the battery charging area, where employee(s) would have to travel around forklifts and pallet jacks, exposing employees to the hazards of corrosive chemical splashes.
Recent events (2)
  • — I (O) $5000
  • — Z (S) $5000

1910.157 C01

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $3000.00 · Current $1500.00 Reduced

Hazardous substances 10601410

29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:    On or about January 23, 2015, in the raw cooler hallway, where employees were charging batteries on forklifts and pallet jacks, and flammable liquid sanitizer was handled by contract employees, Amerex #11 portable fire extinguisher was blocked by stored equipment including a broken pallet jack and portable hoist, exposing employees to the hazards of fire.
Recent events (2)
  • — I (O) $1500
  • — Z (S) $3000

1910.303 G01 I A

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $3000.00 · Current $1500.00 Reduced
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:    On or about January 23, 2015, raw cooler area, Square D Power Panel DP 480-Volt box for the freezer control panel, lighting, and battery chargers and Lighting Panel DL 240/120 V box controlling lighting were blocked by stored equipment including a broken pallet jack and portable hoist.
Recent events (2)
  • — I (O) $1500
  • — Z (S) $3000

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340210582.