OSHA Inspection: WELLS WOOD TURNING & FINISHING

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of WELLS WOOD TURNING & FINISHING in 46 JOHN ELLINGWOOD ROAD, BUCKFIELD, ME 04220 (NAICS 321918). OSHA activity number 340299916.

Watch Wells Wood Turning & Finishing — free Get an email when a new federal OSHA severe-injury report for Wells Wood Turning & Finishing is published. One employer, no account, unsubscribe in one click.
Site address
46 JOHN ELLINGWOOD ROAD
City
BUCKFIELD
State
ME
ZIP
04220
Mailing
P.O. BOX 220, BUCKFIELD, ME 04220
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321918
Employees
34
Ownership type
A

4 citations on file for this inspection.

1910.107 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2975.00 · Current $2083.00 Reduced
29 CFR 1910.107(b)(1): Spray booth(s) were not substantially constructed of steel, concrete or masonry:  Depot Street - The back side of the spray booth was constructed of cardboard.
Recent events (2)
  • — I (S) $2082.5
  • — Z (S) $2975

1910.107 C06

Serious Gravity 5 4 instances 2 exposed
Issued
Abate by
Penalty
Initial $2975.00 · Current $2083.00 Reduced
29 CFR 1910.107(c)(6): Electrical wiring, motors, and other equipment outside of but within twenty (20) feet of any spray area, and not separated therefrom by partitions, produced sparks under normal operating conditions and did not otherwise conform to the provisions of subpart S of this part for Class I, Division 2 Hazardous Locations:  130 Depot Street Building - In the following instances the electrical wiring and equipment located within 20 feet of a flammable liquid spraying operation did not conform to the requirements of Subpart S for a Class I, Division 2 location:      a)    The 110V electrical outlet.     b)    The uncovered junction box.         c)    The conduit without adequate strain relief.     d)    The electrical box containing the on/off switch to the exhaust motor.
Recent events (2)
  • — I (S) $2082.5
  • — Z (S) $2975

1910.125 E01 I

Serious Gravity 5 3 instances 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.125(e)(1)(i): All electrical wiring and equipment in each vapor area and any adjacent area did not conform to the applicable hazardous (classified)-area requirements of subpart S of this part:  130 Depot Street Building - In the following instances the electrical wiring and equipment located in the vapor area of the dipping operation which was using Class I, Division II materials, did not conform to the electrical requirements of Subpart S:      a)    The 110V electrical outlets.     b)    The uncovered junction box.     c)    The conduit which was not threaded properly and lacked strain relief.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 D01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2380.00 · Current $1666.00 Reduced
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):  130 Depot Street Building - The belt and pulley assembly on the exhaust motor for the spray booth was not guarded.