1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: WINCO FOODS, LLC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of WINCO FOODS, LLC. in 2390 E. FREIGHT ST., BOISE, ID 83705 (NAICS 445110). OSHA activity number 340305143.

Watch Winco Foods, LLC. — free Get an email when a new federal OSHA severe-injury report for Winco Foods, LLC. is published. One employer, no account, unsubscribe in one click.
Establishment
WINCO FOODS, LLC.
Site address
2390 E. FREIGHT ST.
City
BOISE
State
ID
ZIP
83705
Mailing
P.O. BOX 5629, BOISE, ID 83705
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
445110
Employees
250
Ownership type
A

7 citations on file for this inspection.

1910.23 A03 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4250.00 · Current $2500.00 Reduced
29 CFR 1910.23(a)(3)(i): 29 CFR 1910.23(a)(3)(i):  When a floor opening was not in use, the hinged floor opening cover was not closed or the exposed side was not guarded at both top and intermediate position by removable standard railings:  a) Compressor Room Roof: On or about 2-11-2015, employees performing regular maintenance on the roof mounted  evaporative condensers, were using the roof mounted hatch access, with a fall distance of approximately 10 feet to the next lower level stairway landing without guard rails, or a procedure to require the hatch to be closed while they were working on the roof.  Note: Abatement certification is required for this item.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $4250

1910.23 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent).  a)  Compressor Room Roof: On or about 2-11-2015, employees were walking daily on the roof deck, approximately 53 inches from the edge of the roof that was approximately 25 feet to the next level without guard rails to perform maintenance on the roof mounted evaporative condensers.   Note: Abatement certification is required for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.119 D03 II

Other-than-serious 40 instances 249 exposed
Issued
Abate by
Penalty
Initial $4250.00 · Current $4250.00
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices.     a) Ammonia Refrigeration System: On or about February 11, 2015, pressure relief devices installed August 2009 had not been replaced or recertified in accordance with Company RAGAGEP IIAR Bulletin 110, Section 6.63, Revision: May 24, 2007.    Note: Abatement certification is required for this item.
Recent events (2)
  • — I (O) $4250
  • — Z (S) $4250

1910.119 E03 IV

Other-than-serious 2 instances 249 exposed
Issued
Abate by
Penalty
Initial $3400.00 · Current $2000.00 Reduced
29 CFR 1910.119(e)(3)(iv): The process hazard analysis did not address the consequences of the failure of engineering and administrative controls:    a) Compressor Room Roof: On or about 2-11-2015, the initial PHA completed on 6-24-2009 and the Revalidation PHA completed 08-06-2014 did not consider the hazard of trapped liquid NH3 by the isolation of EC 1 & 2 that could result in high hydrostatic pressure and the rupture of  the condensers that do not have PRVs to relieve over - pressure in the case of an upset in the system.    Note: Abatement certification is required for this item
Recent events (2)
  • — I (O) $2000
  • — Z (S) $3400

1910.134 C01

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.134(c)(1): A written respiratory protection program that included the provisions in 29 CFR 1910.134(c)(1)(i) - (ix) with worksite specific procedures was not established and implemented for required respirator use:  a) Compressor room: On or about 2-11-2015, an employee was using a North 7600-S full face respirator without a program and specific procedures in place for respirator use while draining oil from oil pots in the NH3 system.  Note: Abatement certification is required for this item.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.134 D01 III

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.134(d)(1)(iii): The employer did not identify and evaluate the respiratory hazard(s) in the workplace; including a reasonable estimate of employee exposures to respiratory hazards and identification of the contaminant's chemical state and physical form:   a) Various locations while servicing NH3 system: On or about 2-4-2015, employees were using respirators while draining oil pots without a reasonable estimate of the employee's potential exposure to NH3.    Note: Abatement certification is required for this item.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.134 F02

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.134(f)(2): Employee(s) using a tight-fitting facepiece respirator were not annually fit tested:   a) Compressor Room and various locations in the NH3 system: On or about 2-4-2015, an employee was using a North 7600-S full face respirator to perform maintenance on the NH3 refrigeration system that was last fit tested on 10-19-2010.  Note: Abatement certification is required for this item.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View WINCO FOODS, LLC.'s full OSHA safety record →