PECOS, TX —
OSHA Inspection: OIL PATCH GROUP
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of OIL PATCH GROUP in BIG E RIG 4, 16.3 MILES S. OF PECOS, PECOS, TX 79772 (NAICS 532412). OSHA activity number 340444819.
Where did this inspection happen?
- Establishment
- OIL PATCH GROUP
- Site address
- BIG E RIG 4, 16.3 MILES S. OF PECOS
- City
- PECOS
- State
- TX
- ZIP
- 79772
- Mailing
- 2425 TOLIVAR STREET, PECOS, TX 79772
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 532412
- Employees
- 2
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $2430.00 · Current $1458.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling: On or about March 4, 2015, at Big-E Rig 4, listed or labeled equipment was not installed and used in accordance with manufacturer instructions exposing employees to electrical shock hazards in the following instances; a. Behind the driller trailer, the 2800-gallon water tanks electric motor pump was wrapped using a heater tape to keep a nozzle from freezing; the heater tape was plugged into a 50-foot orange extension cord. Manufacturer instructions specifically states do not use with extension cords. b. Behind the driller trailer, the 2800-gallon water tanks electric motor pump was plugged into a 50-foot orange extension cord then daisy-chained using another 50-foot red/black extension cord which then plugged into the main site transformer. Manufacturer instructions specifically states do not plug one extension cord into another.
Recent events (2)
- — I (S) $1458
- — Z (S) $2430
1910.304 G05
- Issued
- Abate by
- Penalty
- Initial $2431.00 · Current $1459.00 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: On or about March 4, 2015, at Big-E Rig 4, The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective exposing employees to electrical shock hazards in the following instances; a. Oil Patch Rental trailer OPR 1162 (used by Directional Driller) was not grounded. b. Oil Patch Rental trailer OPR 1101 (used by Mud Engineer) was not grounded.
Recent events (2)
- — I (S) $1458.6
- — Z (S) $2431
1910.305 E02
- Issued
- Abate by
- Penalty
- Initial $2430.00 · Current $1458.00 Reduced
General-duty citation text
29 CFR 1910.305(e)(2): Switches, circuit breakers, and switchboards. Switches, circuit breakers, and switchboards installed in wet locations were not enclosed in weatherproof enclosures. On or about March 4, 2015, at Big-E Rig 4, the employer did not ensure utilized switches, circuit breakers, and switchboards installed in wet locations were enclosed weatherproof enclosures, employees were exposed to electrical shock hazards in the following instances; a. In front of the Oil Patch Rental trailer OPR 1101 (used by Mud Engineer) the cover to the circuit breaker was missing. b. In front of the Oil Patch Rental trailer OPR 1101 (used by Mud Engineer) the cover to the two-120V outlet receptacle box was missing its weatherproof cover.
Recent events (2)
- — I (S) $1458
- — Z (S) $2430
More inspections in this industry (NAICS 532412)
DURHAM, NC—2026-07-08
161503 - SUNBELT RENTALS, INC.
SUNNYVALE, CA—2026-06-11
SUNBELT RENTALS
SOPHIA, WV—2026-06-03
BOYD COMPANY
CRESTWOOD, KY—2026-06-03
69172 - SKYWORKS LLC
WINTERSVILLE, OH—2026-05-20
MURPHY FAMILY INC.
More inspections in TX
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.
FORT WORTH, TX—2026-07-10
RC PROFESSIONAL ROOFING OF TEXAS LLC
CYPRESS, TX—2026-07-10
FEDERICO CARVAJAL GARCIA
SAN ANTONIO, TX—2026-07-10
ED LONG'S METAL WORKS
SAN ANTONIO, TX—2026-07-09
WAREHOUSE RACK COMPANY, LP
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340444819.