Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: HUMANETICS INNOVATIVE SOLUTIONS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of HUMANETICS INNOVATIVE SOLUTIONS, INC. in 900 DENTON DRIVE, HURON, OH 44839 (NAICS 334515). OSHA activity number 340446764.

Watch Humanetics Innovative Solutions, INC. — free Get an email when a new federal OSHA severe-injury report for Humanetics Innovative Solutions, INC. is published. One employer, no account, unsubscribe in one click.
Site address
900 DENTON DRIVE
City
HURON
State
OH
ZIP
44839
Mailing
900 DENTON DRIVE, HURON, OH 44839
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
334515
Employees
160
Ownership type
A

8 citations on file for this inspection.

1910.23 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $4000.00 Reduced
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent):    A)    Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 44839: On or about March 5, 2015, the employer failed to ensure that the open-sided floor of the loft, located above the maintenance room, was equipped with standard railing in accordance with 29 CFR 1910.23(e). Employees were exposed to a fall hazard of approximately 10 feet from the floor of the loft to the concrete floor below.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $4000
  • — Z (S) $5000

1910.147 C07 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $4000.00 Reduced
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program was understood by employees:     A)    Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 44839: On or about March 5, 2015, the employer failed to properly train employees to lockout/tagout equipment such as, but not limited to, the Enco Drill Press (Model 126-2240) located in the Ribs Department, before employees were conducting activities such as, but not limited to, changing drill bits. Employees were exposed to injuries from unexpected start-up of the machine and energy release while electrical energy was not controlled prior to conducting work.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $4000
  • — Z (S) $5000

1910.147 D02

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.147(d)(2): The machine or equipment was not turned off or shut down using the procedures established for the machine or equipment:   A)    Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 44839: On or about March 5, 2015, the employer did not ensure that equipment such as, but not limited to, the Enco Drill Press (Model 126-2240) located in the Ribs Department, was properly turned off/shut down while employees conducted activities such as, but not limited to, changing drill bits. Employees were exposed to injuries from unexpected start-up of the machine and energy release while electrical energy was not controlled prior to conducting work.  In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.332 B01

Serious Gravity 10 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $6000.00 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    A)    Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 44839: On or about December 26, 2014, the employer failed to ensure that maintenance employees were provided with training on electrical safety-related work practices such as, but not limited to, arc flash/blast hazards and protective equipment for the hands, head, and body to protect against electrical hazards while working on or near energized or potentially energized electrical parts.  An employee was exposed to 480 volts/3 phase electrical hazards while wiring the battery charger in the energized electrical panel, located in the maintenance room, without locking the panel out and without proper electrical personal protective equipment.      B)     Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 4839: On or about March 2, 2015, the employer failed to ensure that maintenance employees were provided with training on electrical safety-related work practices such as, but not limited to, electric shock hazards and protective equipment for the hands to protect against electrical hazards while working on or near energized or potentially energized electrical parts.  An employee was exposed to 110 volts electrical hazards while moving electrical conduit and an electrical cord in Materials Department without proper electrical personal protective equipment.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $6000
  • — Z (S) $7000

1910.332 B03

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.332(b)(3): Employees were not trained in and familiar with the safety related work practices required by 29 CFR 1910.331 through 29 CFR 1910.335 that pertained to their respective job assignments:     A)    Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 44839: On or about December 26, 2014, the employer did not ensure that maintenance employees, who were working on or near exposed energized parts, were provided with training for qualified persons in accordance with 29 CFR 1910.332(b)(3). Employees were exposed to electrical hazards of up to 480 volts /3 phase while conducting activities such as, but not limited to, electrical troubleshooting and connecting/wiring equipment.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $6000.00 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:     A)    Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 44839: On or about December 26, 2014, the employer did not ensure that an electrical panel, located in the maintenance room, was disconnected from all electric energy sources when a maintenance employee was wiring the battery charger. The employee was exposed to 480 volts/3 phase electrical hazards.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $6000
  • — Z (S) $7000

1910.335 A01 I

Serious Gravity 10 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $5000.00 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    A)    Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 44839: On or about December 26, 2014, the employer did not ensure that maintenance employee, who was wiring the battery charger in the energized electrical panel located in the maintenance room, was provided with proper electrical personal protective equipment for the hands, head, and body. The employee was exposed to 480 volts/3 phase electrical hazards.      B)     Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 4839: On or about March 2, 2015, the employer did not ensure that maintenance employee, who was moving electrical conduit and an electrical cord  in Materials Department, was provided with proper electrical personal protective equipment for the hands. The employee was exposed to 110 volts electrical hazards.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $5000
  • — Z (S) $7000

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $25000.00 · Current $5000.00 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    A)    Humanetics Innovative Solutions, Inc., located at 900 Denton Drive, Huron, OH 44839: On or about March 5, 2015, the employer failed to ensure that the Enco Drill Press (Model 126-2240), located in the Ribs Department, was properly guarded in order to prevent employees from inadvertently being caught by the rotating chuck during the drill press operation. Employees were exposed to caught-by and amputation hazards.      Humanetics Innovative Solutions, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard (1910.212(a)(1)), which was contained in OSHA Inspection # 313788630, Citation number 1, Item number 2a, and was affirmed as a final order on 09/30/2011, with respect to a workplace located at 900 Denton Drive, Huron, OH 44839.    No additional abatement information is needed for this item.
Recent events (2)
  • — I (S) $5000
  • — Z (R) $25000

View HUMANETICS INNOVATIVE SOLUTIONS, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340446764.