OSHA Inspection: PRECISION ELECTRIC AND LIGHTING

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PRECISION ELECTRIC AND LIGHTING in RITE AID, 101 SOUTH MAIN STREET, NEWARK, NY 14513 (NAICS 238210). OSHA activity number 340493741.

Watch Precision Electric AND Lighting — free Get an email when a new federal OSHA severe-injury report for Precision Electric AND Lighting is published. One employer, no account, unsubscribe in one click.
Site address
RITE AID, 101 SOUTH MAIN STREET
City
NEWARK
State
NY
ZIP
14513
Mailing
8318 LINK ROAD, ROME, NY 13440
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
1
Ownership type
A

12 citations on file for this inspection.

1926.34 C

Serious Gravity 1 8 instances 1 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $840.00 Reduced
29 CFR 1926.34(c): Means of egress was not continually maintained free of all obstructions or impediments to full instant use in the case of fire or other emergency:    a) Entire building, on or about 3-25-15:  One employee worked in a building where multiple floor mounted electrical boxes posed a trip hazard.     ABATEMENT CERTIFICATION IS REQUIRED FOR THIS ITEM
Recent events (2)
  • — I (S) $840
  • — Z (S) $1200

1926.403 B02

Serious Gravity 5 3 instances 1 exposed
Issued
Abate by
Penalty
Initial $2400.00 · Current $1680.00 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) Southwest corner of building, ceiling, on or about 3-25-15:  One employee was working around a 4"x4" box/cord assembly that was not being used as designed or as "listed and labeled".     b) Northwest corner of building, on or about 3-25-15:  One employee was working with and around 4"x 4" box/cord assembly that was not being used as designed or as "listed and labeled".     ABATEMENT CERTIFICATION IS REQUIRED FOR THIS ITEM
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2400

1926.405 A02 II B

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(a)(2)(ii)(B): Temporary wiring branch circuits were laid on the floor:    a) Northwest corner of building, on or about 3-25-15:  Employees were using a branch circuit that was laid on the floor/ground.     ABATEMENT CERTIFICATION IS REQUIRED FOR THIS ITEM
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, and fittings were not protected from abrasion, and openings in boxes, cabinets, and fittings through which conductors entered were not effectively closed:     a) Southwest corner of building, temporary power panel, on or about 3-25-15:  One employee was working with and around a power panel with an unused opening and a wire passing through the metal enclosure, not protected from abrasion.     ABATEMENT CERTIFICATION IS REQUIRED FOR THIS ITEM
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 G02 III

Serious Gravity 5 2 instances 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(g)(2)(iii): Flexible cords were not used in continuous lengths without splice or tap:    a) Southwest corner of building, on or about 3-25-15:  One employee was working around a power panel where a cord used for a permanent lighting was not continuous in length, with an in line splice/repair that was not in a box.       b) Southwest corner of building, on or about 3-25-15:  One employee was working around a power panel where a cord used for a permanent lighting was not continuous in length, connected outside of a 4"x4" junction box.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.404 B01 II

Serious Gravity 5 2 instances 1 exposed
Issued
Abate by
Penalty
Initial $2400.00 · Current $1680.00 Reduced
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection:    a) Southwest corner of building, temporary panel, on or about 3-25-15:  One employee was powering hand held power tools through multiple extension cords and duplex receptacles that were not protected by a ground fault circuit interrupter (GFCI).     ABATEMENT CERTIFICATION IS REQUIRED FOR THIS ITEM
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2400

1926.404 F06

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:    a) West side of building, bathroom area, on or about 3-25-15:  One employee was using an extension cord that did not have a continuous path to ground due to a missing ground pin.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 G01 III

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(g)(1)(iii): Flexible cords and cables were used as a substitute for the fixed wiring of a structure:    a) Southwest corner of building, temporary power panel area, on or about 3-25-15:  Employees were powering store lights using a flexible cord as a substitute for fixed/permanent wiring.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 G01 III B

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(g)(1)(iii)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:    a) Northwest corner of building, on or about 3-25-15:  Employees were using power from a cord that was passed through a wall opening.     ABATEMENT CERTIFICATION IS REQUIRED FOR THIS ITEM
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 E01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2400.00 · Current $1680.00 Reduced
29 CFR 1926.405(e)(1): In wet locations, cabinets, cutout boxes, fittings, boxes and panelboard enclosures were not weatherproof:    a) Northwest corner of building, on or about 3-25-15:  Employees were using a receptacle box that was not weatherproof.       ABATEMENT CERTIFICATION IS REQUIRED FOR THIS ITEM
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2400

1926.405 G02 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws:     a) West end of building, on or about 3-25-15:  Employees were operating various hand held power tools that were plugged into an extension cord that exhibited a broken strain relief.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.416 E01

Serious Gravity 5 2 instances 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables were used:    a) Southwest corner of building, on or about 3-25-15:  One employee was powering lights using an extension cord that was damaged.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340493741.