29 PALMS, CA —
OSHA Inspection: MCAGCC-MAGTFTC, MCCS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MCAGCC-MAGTFTC, MCCS in MCCS GOLF COURSE BOX 788150, 29 PALMS, CA 92278 (NAICS 928110). OSHA activity number 340521871.
Where did this inspection happen?
- Establishment
- MCAGCC-MAGTFTC, MCCS
- Site address
- MCCS GOLF COURSE BOX 788150
- City
- 29 PALMS
- State
- CA
- ZIP
- 92278
- Mailing
- MCCS DIRECTORATE BLDG 1522 MCAGCC - BOX 788150, 29 PALMS, CA 92278
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 120
- Ownership type
- D
Citations
8 citations on file for this inspection.
1910.253 B04 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour. (a) At the MCCS, Golf Course Maintenance Bldg. 2316, oxygen and acetylene gas cylinders were in storage together for more than 30 days.
Recent events (1)
- — Z (S) $0
1910.303 H05 III B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(h)(5)(iii)(B): Permanent and conspicuous warning signs were not provided, reading substantially as follows: "DANGER -- HIGH VOLTAGE -- KEEP OUT." (a) At the MCCS, Golf Course Maintenance Bldg. 2316, the main electrical power panel did have warning signs posted to caution employees of the danger of high voltage.
Recent events (1)
- — Z (S) $0
1910.176 B
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.176(b): Material stored in tiers was not stacked, blocked, interlocked or limited in height so that it was stable and secure against sliding and collapse. (a) At the MCCS, Golf Course Maintenance Bldg. 2316, boxes of materials and a piece of tin extended beyond the top and middle shelves.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. (a) At the MCCS, Golf Course Cart Barn, electrical wall outlet receptacle boxes used for energizing golf carts were not approved for outdoor applications.
Recent events (1)
- — Z (S) $0
1910.304 B03 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in wet locations were not equipped with ground-fault circuit-interrupter protection for personnel. (a) At the MCCS, Golf Course Club House Building 3811, energized electrical outlets next to the sink did not have ground fault circuit interrupter protection for employees.
Recent events (1)
- — Z (S) $0
1910.36 G02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. (a) At the MCCS, Golf Course Club House Bldg. 3811, exit access was 18 inches and obstructed by a safe and a file cabinet.
Recent events (1)
- — Z (S) $0
1910.303 B01 VIII
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(1)(viii): Electric equipment was not free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment was not determined using the following considerations: Other factors that contribute to the practical safeguarding of persons using or likely to come in contact with the equipment. (a) At the MCCS, Golf Course Lunch room trailer 3812Tnear the ceiling, an energized electrical connection had exposed wiring and was not enclosed in a box.
Recent events (1)
- — Z (S) $0
1960.30 A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1960.30(a): 29 CFR 1960.30(a): The Agency did not ensure prompt abatement of unsafe and unhealthful conditions: (a) At the MCCS Golf Course, on 3/2/2011 and again on 3/7/2013, the identified serious hazard involving the anchoring of Trailer 3812T against strong winds was not abated.
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 928110)
FORT LEE, VA—2026-07-15
U.S. DEPARTMENT OF THE ARMY - FORT LEE
COLUMBIA, SC—2026-07-02
U.S. DEPARTMENT OF VETERANS AFFAIRS
COLUMBIA, SC—2026-07-02
U.S. DEPT OF ARMY
COLUMBIA, SC—2026-07-02
U.S. DEPT OF ARMY
EL PASO, TX—2026-06-24
U.S. CUSTOMS AND BORDER PROTECTION
More inspections in CA
EL CAJON, CA—2026-07-16
GRANITE AND MARBLE CONCEPTS INC.
LIVERMORE, CA—2026-07-16
RJMS CORPORATION
BAKERSFIELD, CA—2026-07-16
MAYORGA FARM LABOR SERVICES
SANTA PAULA, CA—2026-07-16
AHUATZI PRODUCE INC.
SANTA PAULA, CA—2026-07-16
MENDOZA PRODUCE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340521871.