HICKMAN, KY —
OSHA Inspection: WEPFER MARINE OF HICKMAN
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of WEPFER MARINE OF HICKMAN in 380 ST. ROUTE 1354, HICKMAN, KY 42050 (NAICS 488390). OSHA activity number 340599679.
Where did this inspection happen?
- Establishment
- WEPFER MARINE OF HICKMAN
- Site address
- 380 ST. ROUTE 1354
- City
- HICKMAN
- State
- KY
- ZIP
- 42050
- Mailing
- PO BOX 13363, MEMPHIS, TN 38113
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 488390
- Employees
- 3
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.253 B04 III
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1800.00 Reduced
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least (a) Wepfer Marine of Hickman - On or about 4/28/15, employees were exposed to explosion hazards when oxygen and acetylene cylinders were not separated as required. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (S) $1800
- — Z (S) $2800
1915.56 B04
- Issued
- Abate by
- Penalty
- Initial $2100.00 · Current $1500.00 Reduced
General-duty citation text
29 CFR 1915.56(b)(4): Welding cable in poor condition was used. a) Wepfer Marine of Hickman- On or about 4/28/15, employees were exposed to electrical hazards when using a welding machine with damaged cables. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (S) $1500
- — Z (S) $2100
1910.106 B02 VII A
- Issued
- Abate by
- Penalty
- Initial $4200.00 · Current $2100.00 Reduced
General-duty citation text
29 CFR 1910.106(b)(2)(vii)(a): Area(s) surrounding tank(s) containing flammable liquids were not provided with adequate drainage or dikes: a) Wepfer Marine of Hickman - On or about 4/28/15, above ground fuel tanks on site and did not have any drainage or diking established to protect adjacent waterways from leakage and/or spillage. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (R) $2100
- — Z (R) $4200
1915.173 D
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1915.173(d): Barriers or guards were not erected to prevent damage to pressure vessels, drums, and other containers of 30 gallon capacity, or over, containing flammable or toxic liquids or gases. a) Wepfer Marine of Hickman - On or about 4/28/15, fuel tanks were not protected against collision damage from vehicles exposing employees to explosion hazards. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (S) $0
- — Z (R) $0
1910.106 D07 I B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.106(d)(7)(i)(b): A portable fire extinguisher having a rating of not less than 12-B units was not located not less than 10 feet, nor more than 25 feet, from any Category 1, 2, or 3 flammable liquid storage area located outside of a storage room but inside a building as required. a) Wepfer Marine of Hickman - On or about 4/28/15, a fire extinguisher was located 3 feet from fuel tanks. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 488390)
WARROAD, MN—2026-05-19
U.S. COAST GUARD SECTOR NORTHERN GREAT LAKES
HOUMA, LA—2026-04-27
AMERICAN RECOVERY LLC
TAOS, NM—2026-03-31
TAOS, TOWN OF
SEATTLE, WA—2026-01-26
WA317989551 - VIGOR INDUSTRIAL LLC
PORTLAND, OR—2025-12-11
DEPT. OF DEFENSE - USACE
More inspections in KY
LOUISVILLE, KY—2026-07-15
69328 - BEST SUPPLY INC
HATTON, KY—2026-07-15
69327 - KENTUCKY STATE POLICE ACADEMY
BARDSTOWN, KY—2026-07-15
69326 - TOWER AUTOMOTIVE OPERATIONS USA I LLC
LOUISVILLE, KY—2026-07-15
69325 - HIGHLAND ROOFING CO INC
OKOLONA, KY—2026-07-14
69324 - CONCO INC
Source