OSHA Inspection: PRO AUTOSOUND & SECURITY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PRO AUTOSOUND & SECURITY in 2271 ELDORADO DRIVE, BILLINGS, MT 59102 (NAICS 443142). OSHA activity number 340795210.

Watch PRO Autosound & Security — free Get an email when a new federal OSHA severe-injury report for PRO Autosound & Security is published. One employer, no account, unsubscribe in one click.
Site address
2271 ELDORADO DRIVE
City
BILLINGS
State
MT
ZIP
59102
Mailing
2271 ELDORADO DRIVE, BILLINGS, MT 59102
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
443142
Employees
6
Ownership type
A

5 citations on file for this inspection.

1910.303 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $960.00 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1):  a) Installation Bay; On or about July 23, 2015 and at times prior, employees were exposed to shock and burn hazards when accessing breakers while reaching over two live conductors energizing an air conditioning unit.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1910.303 F02

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a) Instillation Bay, east panel; on or about July 23, 2015 and at times prior, employees were exposed to the hazards associated with not being able to correctly identify the electrical disconnect switches to de-energize circuits in the event of an emergency.  b) Installation Bay, south panel; on or about July 23, 2015 and at times prior, employees were exposed to the hazards associated with not being able to correctly identify the electrical disconnect switches to de-energize circuits in the event of an emergency.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 F01 VIII

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $960.00 Reduced
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD.":  a) Instillation Bay, east panel; on or about July 23, 2015 and at times prior, employees were exposed to shock hazards while opening and closing lighting circuit breakers.  b) Installation Bay, south panel; on or about July 23, 2015 and at times prior, employees were exposed to shock hazards while opening and closing lighting circuit breakers.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1910.334 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(b)(2): The repetitive manual reclosing of circuit breakers or reenergizing electric power and lighting circuits through replaced fuses was not prohibited:  a) Instillation Bay, east panel; on or about July 23, 2015 and at times prior, employees were exposed to shock hazards while manually reclosing circuit breakers to reenergize electrical power to an air compressor in the mornings and evenings.  b) Installation Bay, south panel; on or about July 23, 2015 and at times prior, employees were exposed to shock hazards while manually reclosing circuit breakers to reenergize electrical power to an air compressor and air conditioner in the mornings and evenings.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 D02

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $960.00 Reduced
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front:  a) Installation Bay; east panel, on or about July 23, 2015 and at times prior, employees were exposed to shock and arc flash while accessing an electrical panel.  b) Installation Bay; south panel, on or about July 23, 2015 and at times prior, employees were exposed to shock and arc flash while accessing an electrical panel.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600