LANCASTER, NH —
OSHA Inspection: WALKER INTERNATIONAL EVENTS, INC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of WALKER INTERNATIONAL EVENTS, INC in 516 MAIN STREET, LANCASTER, NH 03584 (NAICS 711190). OSHA activity number 340830751.
Where did this inspection happen?
- Establishment
- WALKER INTERNATIONAL EVENTS, INC
- Site address
- 516 MAIN STREET
- City
- LANCASTER
- State
- NH
- ZIP
- 03584
- Mailing
- 5525 WACHULA ROAD, MYAKKA CITY, FL 34251
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 711190
- Employees
- 18
- Ownership type
- A
Citations
19 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to struck by and crushing injuries while working in a temporary tensioned-membrane structure during inclement weather: a. Site - Employees were not protected from struck by and crushing injuries where the employer did not erect an adequately secured temporary tensioned-membrane structure (big top circus tent) and did not erect the structure at the Lancaster, NH fairgrounds in accordance with the professional engineer's design and diagram. On or about August 3, 2015, employees working inside the big top circus tent were exposed to struck by and crushing injuries when the big top circus tent collapsed during a hazardous weather event. Prior to this weather event there were 7 warnings broadcasted by the National Weather Service which included hazardous weather outlooks, a severe thunderstorm watch, and severe thunderstorm warnings that anticipated damaging winds in access of 60 mph in this area.
Recent events (3)
- — C (S) $7000
- — F (S) $7000
- — Z (S) $7000
1910.37 B02
- Issued
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a. Site- Employees working inside the big top circus tent were not protected from fire and entrapment hazards where the exits were not marked with exit signs.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.133 A01
- Issued
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.133(a)(1): Protective eye equipment was not required where there was a reasonable probability of injury that could be prevented by such equipment: a. Site- Employees using a pneumatic jack hammer and a sledge hammer to install steel ground stakes for the big top circus tent were not protected from eye injuries where eye protection was not worn.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.157 C01
- Issued
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a. Site- Employees were not protected from fire and entrapment hazards where fire extinguishers were not provided inside the big top circus tent where circus performers were performing with open flames.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.243 B02
- Issued
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.243(b)(2): Airhose and hose connections used for conducting compressed air to utilization equipment was not designed for the pressure and service to which they were subjected. a. Site- Employees using a pneumatic jack hammer, rubber hose, and air compressor to install steel ground stakes were not protected from struck by and laceration injuries were the pressurized air was supplied through a hose that was not marked with a rating for air pressure and was secured to the equipment with metal hose clamps.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a. Site- On or about August 3, 2015 an employee operating sound equipment inside the big top circus tent was not protected from electric shock and burns where two relocatable power taps meant for indoor use in dry locations only were zip tied and daisy chained together. Labeling requirements do not allow for use in wet locations and plugging one power tap into another due to the electric shock and fire hazards.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.303 B07
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(7): Electric equipment was not installed in a neat and workmanlike manner: a. Site- Employees were not protected from electric shock hazards where temporary electrical equipment was not installed and operated safely including, but not limited to, grounding the temporary electrical distribution system, installing waterproof equipment when used outdoors, protecting flexible cords run on the ground, installing strain relief devices, removing damaged electrical equipment from service, properly labeling equipment, protecting outlet receptacles with ground fault circuit interrupters, and only using electrical equipment for its intended purpose.
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
1910.303 B07 IV
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: a. Site- On or about August 3, 2015 employees were not protected from electric shock and burns where two Semcor MFG portable power distribution boxes, operating at 208 volts, were in use after sustaining physical damage with included multiple electrical receptacles with electrical burns and multiple electrical receptacle that were pulled out from the distribution box exposing internal wiring to the environment.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a. Site- Employees were not protected from electric shock where electrical equipment including a double throw safety switch, panel board, load center, and multiple circuit breakers were not labeled to identify their purpose.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.304 B03 II A
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15, 20 and 30-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel did not have ground-fault circuit-interrupter protection for personnel: a. Site- Employees were not protected from electric shock where single phase, 125 volt, 15 ampere receptacle outlets connected to a temporary power service provided by a generator were not protected by ground fault circuit interrupters. On or about August 3, 2015 an employee unplugged an air blower for a bounce house connected to a 125/208 volt, 15 amp electrical receptacle that was located on the ground while it was raining.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.304 G03 II B
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $2800.00
General-duty citation text
29 CFR 1910.304(g)(3)(ii)(B): The frame of a vehicle was not grounded when the generator mounted on the vehicle supplied power to equipment not located on the vehicle and not cord-and plug-connected equipment through receptacles mounted on the vehicle: a. Site- Employees were not protected from electric shock hazards where a vehicle mounted MQ Whisperwatt 70 kva generator supplying 208 volts to multiple panel boards and portable power distribution boxes through flexible cords was not grounded.
Recent events (3)
- — C (S) $2800
- — F (S) $2800
- — Z (S) $2800
1910.304 G06 VI C 1
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.304(g)(6)(vi)(C)(1): 29 CFR 1910.304(g)(6)(vi)(C)(1): Exposed noncurrent-carrying metal parts of cord- and plug-connected equipment, such as refrigerators. freezers. and air conditioners were not grounded: a. Site- Employees working in the concession trailer were not protected from an electric shock hazard where the freezer was plugged into an ungrounded temporary electric system.
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
1910.305 A02 X
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points: a. Site- Employees were not protected from electric shock hazards from a vehicle mounted MQ Whisperwatt 70 kva generator supplying 208 volts to multiple panel boards and portable power distribution boxes through flexible cords that were not protected from damage. On or about August 3, 2015 a flexible cable operating at 208 volts was run on the ground and a metal grandstand was placed directly on the cable.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.305 B01 I
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed: a. Trailer- An employee operating an MQ Whisperwatt 70 kva generator was not protected from electric shock and arc flash injuries where openings in a box mounted to the top of the generator were not closed. Conductors coming out of the top of the left hand generator enter a box and the conductors pass through conduit from the box to a double throw safety switch. The conduit is not connected to the box on the top of the generator. The conduit and box come together next to an opening in the enclosure around the generators exposing the electrical equipment to rain.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a. Site- Employees were not protected from electric shock where a single phase, 125 volt, 15 ampere receptacle outlet connected to a temporary power service provided by a generator was missing a faceplate. On or about August 3, 2015 an employee unplugged an air blower for a bounce house that was plugged into a 125 volt, 15 amp electrical receptacle missing a faceplate.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.305 J02 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: a. Site- Employees were not protected from electric shock where a single phase, 125 volt, 15 ampere receptacle outlet connected to a temporary power service provided by a generator that was not manufactured for outdoor use. On or about August 3, 2015 while it was raining an employee unplugged an air blower for a bounce house that was plugged into a 125 volt, 15 amp electrical receptacle that was not part of a waterproof electrical system.
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
1910.305 J02 VI
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(j)(2)(vi): A receptacle installed in a wet location where the product intended to be plugged into it was not to be attended while in use (for example, sprinkler system controllers, landscape lighting, and holiday lights) did not have an enclosure that was weatherproof with the attachment plug cap inserted or removed: a. Site- Employees were not protected from electric shock where a single phase, 125 volt, 15 ampere receptacle outlet connected to a temporary power service provided by a generator that was not waterproof. On or about August 3, 2015 while it was raining an employee unplugged an air blower for a bounce house that was plugged into a 125 volt, 15 amp electrical receptacle that was not waterproof.
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
1910.305 E01
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $2000.00
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: a. Trailer- An employee operating circuit breakers in a panel board mounted to the wall of the trailer was not protected from electric shock and arc flash injuries where the electrical equipment was not protected from rain and was not waterproof. b. Site- Employees operating circuit breakers in a temporary panel board located on the ground inside the big top circus tent were not protected from electric shock and arc flash injuries where the panel board was not water proof. On or about August 3, 2015 it rained at the site where the panel board located on the ground.
Recent events (3)
- — C (S) $2000
- — F (S) $2000
- — Z (S) $2000
1910.305 E02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(e)(2): Switches, circuit breakers and switchboards installed in wet locations were not enclosed in weatherproof enclosures: a. Trailer- An employee operating a double throw safety switch and circuit breakers in a panel board mounted to the wall of the trailer was not protected from electric shock and arc flash injuries where the electrical equipment was not protected from rain and was not waterproof. b. Site- Employees operating circuit breakers in a temporary panel board located on the ground inside the big top circus tent were not protected from electric shock and arc flash injuries where the panel board was not water proof. On or about August 3, 2015 it rained at the site where the panel board located on the ground.
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 711190)
LAKE GENEVA, WI—2026-01-07
LAKE GENEVA SUGAR SHACK INC.
FRESNO, CA—2025-11-18
21ST DISTRICT AGRICULTURAL ASSOCIATION
BECKET, MA—2025-08-01
JACOB'S PILLOW DANCE FESTIVAL, INC.
TUSKAHOMA, OK—2025-07-14
DEVIN GUTHRIE
WESTON, WI—2025-06-24
SHERIDAN AMUSEMENTS LLC
More inspections in NH
PORTSMOUTH, NH—2026-07-15
RODAS CONSTRUCTION CORP
DOVER, NH—2026-07-15
KNOX MARSH DEVELOPMENT LLC
DOVER, NH—2026-07-15
REAL PRO BUILDERS CONSTRUCTION INC
MERRIMACK, NH—2026-07-15
BURGER KING
MILFORD, NH—2026-07-15
R G EXTERIORS, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340830751.