MILFORD, MA —
OSHA Inspection: PIN HSIAO & ASSOCIATES LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of PIN HSIAO & ASSOCIATES LLC in 146 A S MAIN STREET, MILFORD, MA 01757 (NAICS 311812). OSHA activity number 340858984.
Where did this inspection happen?
- Establishment
- PIN HSIAO & ASSOCIATES LLC
- Site address
- 146 A S MAIN STREET
- City
- MILFORD
- State
- MA
- ZIP
- 01757
- Mailing
- 146 A SOUTH MAIN STREET., MILFORD, MA 01757
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311812
- Employees
- 55
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.263 E01 VIII
- Issued
- Abate by
- Penalty
- Initial $5000.00 · Current $2500.00 Reduced
General-duty citation text
29 CFR 1910.263(e)(1)(viii): Horizontal dough mixer(s) were not equipped with a full enclosure over the bowl while the agitator was in motion: Mixer room, 146 A South Main Street, Milford, MA: On or about August 19, 2015 employees were required to operate a Hobart horizontal dough mixer which was not equipped with a full enclosure over the bowl while the agitator was in motion.
Recent events (2)
- — I (S) $2500
- — Z (S) $5000
1910.303 G01
- Issued
- Abate by
- Penalty
- Initial $3000.00 · Current $1500.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: 146A South Main Street,Milford, MA: On or about August 13, 2015 employees were observed utilizing electrical appliances and equipment whose main power disconnect source was located in a power panel which was blocked by a large, heavy stainless steel table and other appliances.
Recent events (2)
- — I (S) $1500
- — Z (S) $3000
1910.305 B01 I
- Issued
- Abate by
- Penalty
- Initial $3000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: Water Heater, Mixing Area, 146A South Main Street: On or about August 13, 2015 employees were observed working at or near a water heater whose power wires where not protected from abrasion when entering the main power panel of the unit.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Power Panel, Mixing room, 146A South Main Street, Milford, MA: On or about August 13, 2015 employees were observing working at and around a main power distribution panel which had knockouts and unused openings which were not effectively closed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 C04
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface: Wall, Gluten Free processing area, 146A South Main Street, Milford, MA: On or about August 13, 2015 employees were required to work at or around a flush mounted snap switch which had a damaged faceplate exposing employees to electrical shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J03 I
- Issued
- Abate by
- Penalty
- Initial $5000.00 · Current $2500.00 Reduced
General-duty citation text
29 CFR 1910.305(j)(3)(i): Appliances had live parts normally exposed to employee contact: Hobart horizontal, dough mixer, Mixing Room, 146A South Main Street, Milford, MA: employees were required to use a Hobart mixer which had live parts exposed to areas normally contacted by employees.
Recent events (2)
- — I (S) $2500
- — Z (S) $5000
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Scale, Mixing Room, 146A South Main Street, Milford, MA: On or about August 13, 2015 employees were observed working at or around flexible cords which were used as a substitute for permanent wiring.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 311812)
LONGVIEW, WA—2026-07-10
WA317992033 - UNITED STATES BAKERY DBA FRANZ FAMILY BAKERIE
GLENDALE, CA—2026-07-08
FREUND BAKING COMPANY
YONKERS, NY—2026-07-07
GREYSTON BAKERY INC.
JACKSONVILLE, OR—2026-07-02
317744689 - CURLY TOP BAKE SHOP LLC
MERIDEN, CT—2026-07-02
PUB DISTRIBUTION HOLDER, LLC
More inspections in MA
WORCESTER, MA—2026-07-10
QUINSIGAMOND COMMUNITY COLLEGE
FITCHBURG, MA—2026-07-10
KELLEY WOOD PRODUCTS, INC.
EVERETT, MA—2026-07-10
HORIZON RETAIL CONSTRUCTION INC
NORTON, MA—2026-07-09
DYNAMIC RESIDENTIAL ROOF MARKETING, LLC
NORTON, MA—2026-07-09
LM GENERAL CONSTRUCTION INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340858984.