SAUGUS, MA —
OSHA Inspection: TRIPLE PLAY CONCEPTS, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TRIPLE PLAY CONCEPTS, LLC in 421 BROADWAY STREET, SAUGUS, MA 01906 (NAICS 722211). OSHA activity number 340880053.
Where did this inspection happen?
- Establishment
- TRIPLE PLAY CONCEPTS, LLC
- Site address
- 421 BROADWAY STREET
- City
- SAUGUS
- State
- MA
- ZIP
- 01906
- Mailing
- 421 BROADWAY STREET, SAUGUS, MA 01906
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 722211
- Employees
- 18
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.36 D01
- Issued
- Abate by
- Penalty
- Initial $4900.00 · Current $4900.00
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: Location: Back exit door. On or about August 26, 2015, the back exit door was found locked by a slide bolt that was difficult to open, blocking safe egress for employees in the event of a fire or other emergency.
Recent events (1)
- — Z (S) $4900
1910.37 A03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: Trash cart, boxes routinely left to obstruct the back door exit route. Location: Rear exit door. On or about 8/26/2015, the rear exit route and back exit door was found blocked by a trash cart with debris.
Recent events (1)
- — Z (S) $0
1910.36 G02
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $2800.00
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. (a) Location: Exit route aisle leading from front of service area to rear kitchen prep area. On or about 8/26/2015, the exit access aisle leading from the front service area to the rear of the kitchen prep and cook area did not meet minimum width requirements, measuring 19 inches in width in one area and 17 inches in width in another area due to obstructions protruding into aisle, blocking employees from safe egress in the event of a fire or other evacuation. (b) Location: Exit route aisle leading from rear kitchen prep area to rear exit door. On or about 8/26/2015, the exit access aisle leading from the rear of the kitchen prep area to the rear exit door did not meet minimum width requirements, measuring 23 inches in width, exposing employees to potential hazards in the event of an emergency evacuation.
Recent events (1)
- — Z (S) $2800
1910.305 G01 IV B
- Issued
- Abate by
- Penalty
- Initial $3500.00 · Current $3500.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors: LOCATION: Rear prep area wall in kitchen adjacent to Manager's office. On or about 8/26/2015, the flexible electrical cord/cable was found routed through the ceiling and across the room and down the wall to an outlet, exposing employees to electrical hazards, potential fire hazards.
Recent events (1)
- — Z (S) $3500
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: LOCATION: Rear prep area wall in kitchen adjacent to Manager's office. On or about August 26, 2015, the flexible electrical cord/cable was found with excess strain on the sheath exposing the internal wires, due to shelving unit pressed up against the cord, exposing employees to electrical hazards and shock potential.
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 722211)
SEATTLE, WA—2026-07-08
WA317991985 - IVARS INC
COOS BAY, OR—2026-07-07
317744705 - WEBER ENTERPRISES INC
BELLEVUE, WA—2026-07-01
WA317991887 - PAN WASHINGTON LLC
BEND, OR—2026-06-26
317744659 - LUMINIS ENTERPRISES LLC
BAINBRIDGE ISLAND, WA—2026-06-23
WA317991773 - G & G RESTAURANTS LLC
More inspections in MA
WORCESTER, MA—2026-07-10
QUINSIGAMOND COMMUNITY COLLEGE
FITCHBURG, MA—2026-07-10
KELLEY WOOD PRODUCTS, INC.
EVERETT, MA—2026-07-10
HORIZON RETAIL CONSTRUCTION INC
NORTON, MA—2026-07-09
DYNAMIC RESIDENTIAL ROOF MARKETING, LLC
NORTON, MA—2026-07-09
LM GENERAL CONSTRUCTION INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340880053.