1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: CH BRADSHAW CO.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CH BRADSHAW CO. in 2004 HENDRIX DR, GROVE CITY, OH 43123 (NAICS 336390). OSHA activity number 340939875.

Watch CH Bradshaw CO. — free Get an email when a new federal OSHA severe-injury report for CH Bradshaw CO. is published. One employer, no account, unsubscribe in one click.
Establishment
CH BRADSHAW CO.
Site address
2004 HENDRIX DR
City
GROVE CITY
State
OH
ZIP
43123
Mailing
2004 HENDRIX DR, GROVE CITY, OH 43123
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336390
Employees
21
Ownership type
A

2 citations on file for this inspection.

1910.106 E02 III

Deleted Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $1700.00 · Current $0.00 Reduced
29 CFR 1910.106(e)(2)(iii): "Separation and protection." Areas in which flammable liquids are transferred from one tank or container to another container shall be separated from other operations in the building by adequate distance or by construction having adequate fire resistance. Drainage or other means shall be provided to control spills. Adequate natural or mechanical ventilation shall be provided.    a. At the workplace in the shed area, methanol was dispensed daily by employees from a steel drum without having drains or containment means in place to controls spills.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1700

1910.106 E06 II

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $1700.00 · Current $1190.00 Reduced
29 CFR 1910.106(e)(6)(ii): Grounding. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall not be dispensed into containers unless the nozzle and container are electrically interconnected. Where the metallic floorplate on which the container stands while filling is electrically connected to the fill stem or where the fill stem is bonded to the container during filling operations by means of a bond wire, the provisions of this section shall be deemed to have been complied with.  a. At the workplace in the shed area, methanol was dispensed by employees, several times daily, from a steel drum into a plastic container, without being electrically interconnected by means of a bonding wire or grounded. Methanol was pumped from the drum while employees held the plastic container.  b. At the workplace in the outdoor truck area, methanol was dispensed by employees, several times daily, from a plastic container into propane tanker trucks, without being electrically interconnected by means of a bonding wire or grounded. Methanol was dumped into the tanks through the top hatch or vent prior to filling with propane.
Recent events (2)
  • — I (S) $1190
  • — Z (S) $1700

View CH BRADSHAW CO.'s full OSHA safety record →