Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WEST TEXAS REFRIGIRATION, INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of WEST TEXAS REFRIGIRATION, INC in 2420 EAST SLATON HIGHWAY, LUBBOCK, TX 79404 (NAICS 811310). OSHA activity number 340944339.

Watch West Texas Refrigiration, INC — free Get an email when a new federal OSHA severe-injury report for West Texas Refrigiration, INC is published. One employer, no account, unsubscribe in one click.
Site address
2420 EAST SLATON HIGHWAY
City
LUBBOCK
State
TX
ZIP
79404
Mailing
2420 EAST SLATON HIGHWAY, LUBBOCK, TX 79404
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811310
Employees
16
Ownership type
A

3 citations on file for this inspection.

1910.106 B06

Serious Gravity 10 2 instances 1 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $3430.00 Reduced
29 CFR 1910.106(b)(6): In locations where flammable vapors may be present, precautions were not taken to prevent ignition by eliminating or controlling sources of ignition.  Sources of ignition may include open flames, lightning, smoking, hot surfaces, frictional heat, sparks (static, electrical, and mechanical), spontaneous ignition, chemical and physical-chemical reactions, and radiant heat.    The employer did not ensure that employees were protected from fire hazards while working with flammable liquids and vapors with sources of ignition in the south bay in the following instances:    a) Alkota Cleaner Model 216X4    b) Lighting overhead and emergency lighting over the exit door
Recent events (2)
  • — I (S) $3430
  • — Z (S) $4900

1910.106 E07 I B

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $3430.00 Reduced
29 CFR 1910.106(e)(7)(i)(b): Locations where flammable vapor-air mixtures exist under normal operations were not classified Class I, Division 1 five feet in all directions from all points of vapor liberation.    The employer did not ensure that employees were protected from fire hazards while working with flammable liquids and vapors with sources of ignition in the south bay were classified as Class 1, Division 1 within five feet of the point of vapor liberation from a tanker containing Pentane.
Recent events (2)
  • — I (O) $3430
  • — Z (S) $4900

1910.307 C

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $3430.00 Reduced
29 CFR 1910.307(c): Equipment, wiring and installations of equipment in hazardous (classified) locations was not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location.    The employer did not ensure that employees were protected from fire hazards while working with flammable liquids and vapors where wiring and lighting was not approved for the location (Class 1, Division 2).
Recent events (2)
  • — I (O) $3430
  • — Z (S) $4900

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340944339.