OSHA Inspection: WLCI ELECTRICAL INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of WLCI ELECTRICAL INC. in 327 SUNSET RD, SAN ANTONIO, TX 78209 (NAICS 238210). OSHA activity number 340980804.
Where did this inspection happen?
- Establishment
- WLCI ELECTRICAL INC.
- Site address
- 327 SUNSET RD
- City
- SAN ANTONIO
- State
- TX
- ZIP
- 78209
- Mailing
- 6030 BETHELVIEW RD # 104, CUMMING, GA 30040
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 10
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.404 B01 II
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites: a) Along the interior north center side first floor of the residential construction building, on or about October 07, 2015, employees were exposed to electrical shock hazards of 120 volts, from a 4" X 4" metal junction box with a broken ground fault interrupter and exposed electrical parts while plugging in equipment into the electrical box. b) Along the interior north center side second floor of the residential construction building, on or about October 07, 2015, employees were exposed to electrical shock hazards of 120 volts, from a 4" X 4" metal junction box with a broken ground fault interrupter and exposed electrical parts while plugging in equipment into the electrical box. c) Along the interior south center side second floor of the residential construction building, on or about October 07, 2015, employees were exposed to electrical shock hazards of 120 volts, from a 4" X 4" metal junction box with a broken ground fault interrupter and exposed electrical parts while plugging in equipment into the electrical box. d) Along the interior south center side third floor of the residential construction building, on or about October 07, 2015, employees were exposed to electrical shock hazards of 120 volts, from a 4" X 4" metal junction box with a broken ground fault interrupter and exposed electrical parts while plugging in equipment into the electrical box.
Recent events (1)
- — Z (S) $4500
1926.405 B01
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed; and conductors entering boxes, cabinets, and fittings were not protected from abrasion: a) Along the interior north center side of the residential construction building, on or about October 07, 2015, employees were exposed to electrical shock hazards of 120 volts from an open and unused circuit breaker blanks, from a Square D electrical circuit box category number HOMC24UC, while accessing an electrical panel during electrical installation of temporary wiring. b) Along the exterior east side of the residential construction building, on or about October 07, 2015, employees were exposed to electrical shock hazards of 120 volts, from a Square D electrical circuit box category number 4O265-761-01, that had an energized Romex wire conductor running through an opening without any type of abrasion protection along the bottom of the box. while accessing an electrical panel during electrical installation of temporary wiring. c) Along the exterior south west side of the residential construction building, on or about October 07, 2015, employees were exposed to electrical shock hazards of 120 volts, from a Square D electrical circuit box category number 4O273-834-02, with an opening without a knockout seal along the bottom of the box while accessing an electrical panel during electrical installation of temporary wiring.
Recent events (1)
- — Z (S) $4500
1926.405 B02
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, or fittings were not provided with covers and in energized installations each outlet box did not have a cover, faceplate, or fixture canopy: Along the interior south center side third floor of the residential construction building, on or about October 07, 2015, employees conducting electrical installation were exposed to electrical hazards of 120 volts from an uncovered outlet source with exposed live parts.
Recent events (1)
- — Z (S) $4500
More inspections at WLCI ELECTRICAL INC.
COLUMBIA, SC—2014-05-08 00:00:00
WLCI ELECTRICAL INC
View WLCI ELECTRICAL INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
PARKVILLE, MD—2026-07-15
THE POWER SOURCE, INC.
SOUTH BARRINGTON, IL—2026-07-15
EDGE ELECTRICAL SYSTEMS, LLC
LAYTON, UT—2026-07-14
LYNN WOODWARD ELECTRIC LLC
BRIDGEPORT, WV—2026-07-14
INFINITY ELECTRIC & SERVICE COMPANY, LLC
ANNAPOLIS, MD—2026-07-14
J.M. MULLEN ELECTRICAL SERVICES, INC.
More inspections in TX
WICHITA FALLS, TX—2026-07-16
UNITED RENTALS, INC.
SAN MARCOS, TX—2026-07-16
CASA MECHANICAL SERVICES, LTD.
CLARKSVILLE, TX—2026-07-15
SEQUOIAS TREE EXPERT LLC
EL PASO, TX—2026-07-15
SURE STEEL
CORPUS CHRISTI, TX—2026-07-15
NORTH STAR ENERGY SOLUTIONS LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340980804.