OSHA Inspection: CHAMPION ELECTRICAL SOLUTIONS, LLC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of CHAMPION ELECTRICAL SOLUTIONS, LLC in 180 UTOPIA CIRCLE, MERRITT ISLAND, FL 32953 (NAICS 238210). OSHA activity number 340985969.

Watch Champion Electrical Solutions, LLC — free Get an email when a new federal OSHA severe-injury report for Champion Electrical Solutions, LLC is published. One employer, no account, unsubscribe in one click.
Site address
180 UTOPIA CIRCLE
City
MERRITT ISLAND
State
FL
ZIP
32953
Mailing
1702 EDITH STREET NE, PALM BAY, FL 32907
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

4 citations on file for this inspection.

1926.21 B02

Serious Gravity 10 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury:  a) 180 Utopia Circle, Merritt Island, FL Job Site - An employee working near live exposed circuits was not provided electrical safety hazard training, on or about October 12, 2015.
Recent events (1)
  • — Z (S) $2800

1926.403 H

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2400.00 · Current $2400.00
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident:  a) 180 Utopia Circle, Merritt Island, FL Job Site - The panel that was powering the boat dock had breaker switches that were not labeled, on or about October 12, 2015.
Recent events (1)
  • — Z (S) $2400

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6300.00 · Current $6300.00
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:  a) 180 Utopia Circle, Merritt Island, FL Job Site - An employee was electrocuted while pulling unenergized wiring through a junction box that contained live 120 volt AC wiring, on or about October 12, 2015.
Recent events (1)
  • — Z (S) $6300

1926.417 A

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged:  a) 180 Utopia Circle, Merritt Island, FL. Job Site - The panel that was powering the boat dock had breaker switches that were not tagged out, on or about October 12, 2015.
Recent events (1)
  • — Z (S) $2800