Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: JBS ELECTRICAL, INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of JBS ELECTRICAL, INC. in 207 N RAMBLING FORK STREET, WEATHERFORD, TX 76087 (NAICS 238210). OSHA activity number 341109502.

Watch JBS Electrical, INC. — free Get an email when a new federal OSHA severe-injury report for JBS Electrical, INC. is published. One employer, no account, unsubscribe in one click.
Site address
207 N RAMBLING FORK STREET
City
WEATHERFORD
State
TX
ZIP
76087
Mailing
207 N RAMBLING FORK STREET, WEATHERFORD, TX 76087
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

3 citations on file for this inspection.

1910.333 A

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $1800.00 · Current $1080.00 Reduced
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:  At the host employers job site, the employer did not ensure electrical employees assigned to troubleshoot and repair the Induction Furnace, 480 Volt Service Disconnect #3 of 6, were provided with a safe method from either direct or indirect electrical contacts when working on or near energized 480 Volts 3 Phase electrical panels exposing employees to arc blast and/or electrical shock hazards.
Recent events (2)
  • — I (S) $1080
  • — Z (S) $1800

1910.333 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $1800.00 · Current $1080.00 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de-energized before the employee worked on or was near to them:  At the host employers job site, the employer did not ensure the 480 Volt Service Disconnect #3 of 6 was completely de-energized prior to allowing any employees to work on or near the energized 480 Volts 3 Phase electrical panels exposing employees to electrical shock and/or arc blast hazards.
Recent events (2)
  • — I (S) $1080
  • — Z (S) $1800

1910.335 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $1800.00 · Current $1080.00 Reduced
29 CFR 1910.335(a)(1): Employees working in areas where there were potential electrical hazards were not provided with, and/or did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  At the host employers job site, the employer did not ensure employees assigned to troubleshoot and repair the 480 Volt Service Disconnect #3 of 6 were provided and used personal protective equipment associated to the hazards of working on or near energized 480 Volts 3 Phase electrical panels exposing employees to arc blast and/or electrical shock injuries.
Recent events (2)
  • — I (S) $1080
  • — Z (S) $1800

View JBS ELECTRICAL, INC.'s full OSHA safety record →