1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: ALBERTSON'S

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ALBERTSON'S in 1300 E. PARK AVENUE, ANACONDA, MT 59711 (NAICS 445110). OSHA activity number 341134237.

Watch Albertson'S — free Get an email when a new federal OSHA severe-injury report for Albertson'S is published. One employer, no account, unsubscribe in one click.
Establishment
ALBERTSON'S
Site address
1300 E. PARK AVENUE
City
ANACONDA
State
MT
ZIP
59711
Mailing
500 E. BAYBROOK CT., BOISE, ID 83706
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
445110
Employees
120000
Ownership type
A

6 citations on file for this inspection.

1910.37 B05

Serious Gravity 5 6 instances 20 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $5000.00
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use:  (a) West Receiving: On or about December 15, 2015 and at times prior, employees were exposed to entrapment hazards while working in the receiving area and the Southwest door was not labeled "Not an Exit".                                     (b) East Receiving: On or about December 15, 2015 and at times prior, employees were exposed to entrapment hazards while working in the receiving area and the Southeast door was not labeled "Not an Exit".                                       (c) North Receiving: On or about December 15, 2015 and at times prior, employees were exposed to entrapment hazards while working in the receiving area and the women's restroom door was not labeled "Not an Exit".                          (d) Receiving: On or about December 15, 2015 and at times prior, employees were exposed to entrapment hazards while working in the receiving area and the men's restroom door was not labeled "Not an Exit".                                     (e) Meat Department: On or about December 15, 2015 and at times prior, employees were exposed to entrapment hazards while working in the receiving area and the meat department door was not labeled "Not an Exit".                                     (f) Freezer: On or about December 15, 2015 and at times prior, employees were exposed to entrapment hazards while working in the receiving area and the bakery freezer door was not labeled "Not an Exit".
Recent events (1)
  • — Z (S) $5000

1910.37 B06

Serious Gravity 5 2 instances 40 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  (a) Bakery: On or about December 15, 2015 and at times prior, employees were exposed to entrapment hazards when the designated emergency exit was not illuminated to be clearly visible in the event of an emergency.                                              (b) Back Office: On or about December 15, 2015 and at times prior, employees were exposed to entrapment hazards when the designated emergency exit was not illuminated to be clearly visible in the event of an emergency.
Recent events (1)
  • — Z (S) $0

1910.38 B

Serious Gravity 5 1 instance 40 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.38(b): An emergency action plan was not in writing, kept in the workplace, and available to employees for review:  (a) All areas: On or about December 15, 2015 and at times prior, employees were exposed to entrapment hazards while working in the store and were not provided a written emergency action plan.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $4000.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Receiving: On or about December 15, 2015 and at times prior, employees were exposed to shock hazards while using an improperly installed receptacle to energize the printer.
Recent events (1)
  • — Z (S) $4000

1910.305 B02 I

Serious Gravity 5 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  (a) Receiving: On or about December 15, 2015 and at times prior, employees were exposed to shock hazards while walking and working in and around unguarded electrical wires.
Recent events (1)
  • — Z (S) $0

1910.305 C04

Serious Gravity 5 1 instance 40 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(c)(4): Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface:  (a) Receiving: On or about December 15, 2015 and at times prior, employees were exposed to shock hazards while using an unguarded light switch:
Recent events (1)
  • — Z (S) $0

View ALBERTSON'S's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341134237.