Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: JVA SERVICES, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of JVA SERVICES, LLC in 616 H ST., NE, WASHINGTON, DC 20002 (NAICS 238210). OSHA activity number 341147411.

Watch JVA Services, LLC — free Get an email when a new federal OSHA severe-injury report for JVA Services, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
JVA SERVICES, LLC
Site address
616 H ST., NE
City
WASHINGTON
State
DC
ZIP
20002
Mailing
1505 REDFORD DR., FORT WASHINGTON, MD 20744
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
7
Ownership type
A

3 citations on file for this inspection.

1926.404 B01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1926.404(b)(1)(i): The employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors:   a)  First Floor, East Grocery - On or about 12/30/2015, an electrician using a portable electric band saw that was not provided with a continuous ground was not protected from electrical hazard by either an assured equipment grounding conductor program or ground fault circuit interrupters.   In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet).
Recent events (1)
  • — Z (S) $2800

1926.404 F06

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:   a)  Ground Floor, East Grocery -  On or about 12/30/2015, an electrician using a portable electric band saw with  the ground pin removed from the saw's attachment plug.   In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet).
Recent events (1)
  • — Z (S) $0

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $4900.00
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:   a)  Main Service Entrance, Building #2 Disconnect - On or about 12/30/2015, two electricians were terminating cables in a disconnect enclosure which contained 208 volt/600 amp live parts and did not first either de-energize the line side of the circuit or use appropriate personal protective equipment and procedures for working on or near to energized parts.   In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet), in addition, documentation demonstrating the abatement is complete must be included with your certification.  This documentation may include, but is not limited to evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (1)
  • — Z (S) $4900

MACY'S

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341147411.