Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: NEIL OIL CO., INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of NEIL OIL CO., INC. in 400 S. FRONT ST. ADM BARGE DOCK, QUINCY, IL 62301 (NAICS 454310). OSHA activity number 341312577.

Watch Neil OIL CO., INC. — free Get an email when a new federal OSHA severe-injury report for Neil OIL CO., INC. is published. One employer, no account, unsubscribe in one click.
Establishment
NEIL OIL CO., INC.
Site address
400 S. FRONT ST. ADM BARGE DOCK
City
QUINCY
State
IL
ZIP
62301
Mailing
418 N FAIR ST, MENDON, IL 62351
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
454310
Employees
30
Ownership type
A

4 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $7000.00
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire hazards while transferring diesel fuel:  On or about March 4, 2016, the liquid transfer equipment used to transfer No. 2 Ultra Low Sulfur Diesel fuel from storage tank #62 to a fuel delivery truck exposed employees to the hazards associated with fire. The fuel delivery nozzle was not listed/approved in that it would not automatically shut off thus allowing fuel to continuously dispense until a valve was manually closed, the hose used to transfer the fuel was not fuel rated, and the pump did not have any pressure relief discharge causing the fuel filter to blow out during the incident.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7000

1910.106 E06 I

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $7000.00
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors:  On or about March 4, 2016, an ADM employee assisting in a transfer of No. 2 Ultra Low Sulfur Diesel, a Category 3 flammable liquid, was exposed to injury when a static discharge ignited fuel vapors and no precautions had been taken to prevent the ignition of flammable vapors from sources of ignition including, but not limited to, static sparks.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7000

1910.132 D01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $500.00 Reduced
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE):    On or about March 4, 2016, a Neil Oil Co., Inc. employee engaged in transferring No. 2 Ultra Low Sulfur Diesel, a category 3 flammable liquid, and the employer had not conducted a hazard assessment and determined the personal protective equipment requirements to protect the employee from the hazards associated with transferring flammable liquids at.
Recent events (2)
  • — I (S) $500
  • — Z (S) $2800

1910.1200 E01

Serious Gravity 5 1 instance 30 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $500.00 Reduced
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:
Recent events (2)
  • — I (S) $500
  • — Z (S) $2800

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341312577.