Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: KEANE REFRIGERATED LOGISTICS, LLC

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of KEANE REFRIGERATED LOGISTICS, LLC in 24 FRONTIER DRIVE, GIBSONIA, PA 15044 (NAICS 493120). OSHA activity number 341343176.

Watch Keane Refrigerated Logistics, LLC — free Get an email when a new federal OSHA severe-injury report for Keane Refrigerated Logistics, LLC is published. One employer, no account, unsubscribe in one click.
Site address
24 FRONTIER DRIVE
City
GIBSONIA
State
PA
ZIP
15044
Mailing
19420 FRAZIER DRIVE, ROCKY RIVER, OH 44116
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
75
Ownership type
A

8 citations on file for this inspection.

1910.119 D03 I E

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3741.00 · Current $1875.00 Reduced
29 CFR 1910.119(d)(3)(i)(E): The employer did not have a compilation for written process safety information pertaining to the ventilation system design:    a) In the facility, on or about March 23, 2016 - The employer was unable to locate or produce process safety information pertaining to the ventilation system design for the ammonia system.
Recent events (3)
  • — F (S) $1875
  • — C (S) $3741
  • — Z (S) $3741

1910.119 D03 II

Deleted Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3741.00 · Current $0.00 Reduced
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices:  a) Machine Room, on or about March 23, 2016 -  The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP) in that the ammonia machinery room was not equipped with a tight-fitting door near the rear of the machinary room.  ANSI/ASHRAE Standard 15-2010, Section 8.12, Paragraph D, is an applicable RAGAGEP that describes the requirements.
Recent events (3)
  • — F (S) $0
  • — C (S) $3741
  • — Z (S) $3741

1910.119 E01

Serious Gravity 1 1 instance 1 exposed
Issued
Penalty
Initial $3741.00 · Current $1875.00 Reduced
29 CFR 1910.119(e)(1): The employer did not perform an initial process hazard analysis (hazard evaluation) on processes covered by 29 CFR 1910.119:     a) In the facility, on or about March 23, 2016 - The employer did not perform an initial process hazard analysis (hazard evaluation) for the facility refrigeration system utilizing anhydrous ammonia and covered by the requirements of 29 CFR 1910.119.
Recent events (3)
  • — F (S) $1875
  • — C (S) $3741
  • — Z (S) $3741

1910.119 F01

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3741.00 · Current $1875.00 Reduced
29 CFR 1910.119(f)(1): The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information and addressing at least steps for each operating phase, safe operating limits, safety and health considerations, and safety systems and their functions as outlined by this paragraph:    a) In the facility, on or about March 23, 2016 - The employer did not develop and implement written operating procedures for activities such as but not limited to inbounding ammonia.
Recent events (3)
  • — F (S) $1875
  • — C (S) $3741
  • — Z (S) $3741

1910.119 F04

Deleted Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3741.00 · Current $0.00 Reduced
29 CFR 1910.119(f)(4): The employer did not develop and implement safe work practices to provide for the control of hazards during operations such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel:  a) In the facility, on or about March 23, 2016 - The employer did not develop or implement specific procedures for removing oil from piping and equipment where oil is likely to collect that is specific for each drain point.
Recent events (3)
  • — F (S) $0
  • — C (S) $3741
  • — Z (S) $3741

1910.119 J04 II

Deleted Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3741.00 · Current $0.00 Reduced
29 CFR 1910.119(j)(4)(ii): Inspection and testing procedures did not follow recognized and generally accepted good engineering practices:  a) In the facility, on or about March 23, 2016 - The company did not follow RAGAGEP, IIAR 110 Section 6.2, while conducting inspections of the ammonia system.
Recent events (3)
  • — F (S) $0
  • — C (S) $3741
  • — Z (S) $3741

1910.119 J05

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3741.00 · Current $1875.00 Reduced
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) before use:    a) In the facility, on or about March 23, 2016 - The piping system showed evidence of external corrosion, including excessive ice build-up.
Recent events (3)
  • — F (S) $1875
  • — C (S) $3741
  • — Z (S) $3741

1910.119 O01

Deleted Serious Gravity 1 1 instance 1 exposed
Issued
Penalty
Initial $3741.00 · Current $0.00 Reduced
29 CFR 1910.119(o)(1): The employer did not certify that they have evaluated compliance with the provisions of this section at least every three years:  a) In the facility, on or about March 23, 2016 - The employer did not certify that they had evaluated compliance with the provisions of 29 CFR 1910.119 at least every three years to verify that the procedures and practices developed under the standard are adequate and are being followed.