Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: LOWES HOME CENTERS, INC. #2513

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of LOWES HOME CENTERS, INC. #2513 in 6400 BRODIE LANE, AUSTIN, TX 78745 (NAICS 444110). OSHA activity number 341365476.

Watch Lowes Home Centers, INC. #2513 — free Get an email when a new federal OSHA severe-injury report for Lowes Home Centers, INC. #2513 is published. One employer, no account, unsubscribe in one click.
Site address
6400 BRODIE LANE
City
AUSTIN
State
TX
ZIP
78745
Mailing
6400 BRODIE LANE, AUSTIN, TX 78745
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
444110
Employees
180
Ownership type
A

4 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 2 instances 180 exposed
Issued
Abate by
Penalty
Initial $3300.00 · Current $1980.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  On or about 31 March 2016, and at times prior thereto, the employer allowed electrical equipment to be used in a manner not in accordance with the manufacturer's instructions included in the listing or labeling, exposing employees to an electrical hazard of approximately 120 volts. 1) Training Room: A re-locatable power tap was zip tied to the metal frame of the workstation rendering the power strip as permanent instead of temporary wiring. 2) Electrical/Lighting: A re-locatable power tap, extension cord, and three-way splitter were connected in series to provide power to a light fixture display at the end of the aisle, creating a daisy chain configuration.
Recent events (2)
  • — I (S) $1980
  • — Z (S) $3300

1910.303 B07 IV

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(7)(iv): 29 CFR 1910.303(b)(7)(iv): Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.  On or about 31 March 2016, and at times prior thereto, the employer allowed damaged electrical energized parts to be used within the facility, exposing employees to an electrical hazard of approximately 120 volts. Receiving Bay 2 had an extendable dock light used for trailers in which the plug for the light and the light switch were separated from the metal frame of the arm. In this condition, the sheathed wires were visible but in close contact with sharp edges of the metal frame.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 A02 IX

Serious Gravity 1 3 instances 8 exposed
Issued
Abate by
Penalty
Initial $3300.00 · Current $1980.00 Reduced
29 CFR 1910.305(a)(2)(ix): All lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lamp holder with a guard.  On or about 31 March 2016, and at times prior thereto, overhead fluorescent lights located at various areas within the store were missing guards to prevent accidental contact or breakage, exposing employees to the hazards of cuts or blindness from falling shards of glass. 1) Aisle 14, Bays 6 through 10 had bulbs that were unprotected at a height of approximately 88 inches high (7 feet 4 inches) or less. 2) Aisle 15, Bay 19 had bulbs that were unprotected at a height of approximately 88 inches high (7 feet 4 inches) or less. 3) Aisle 59, Tool World, Bays 13 through 31 had bulbs that were unprotected at a height of approximately 88 inches high (7 feet 4 inches) or less.
Recent events (2)
  • — I (S) $1980
  • — Z (S) $3300

1910.305 A02 X

Serious Gravity 1 2 instances 37 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(a)(2)(x):  Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points.  On or about 31 March 2016, and at times prior thereto, flexible cords were not protected from accidental damage, exposing the employees working within the area to an electrical hazard of approximately 120 volts. 1) Within the Paint area, a workstation with wheels had been pushed up against a flexible cord that was plugged in at the time of the inspection, smashing the cord into an approximate 90 degree angle. 2) Within Outside Garden, Register 21, a power strip cord was setup so the cord ran through an open metal hole within the cashier's workstation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341365476.