LIMA, OH —
OSHA Inspection: ST. RITA'S HEALTH PARTNERS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ST. RITA'S HEALTH PARTNERS in 730 W. MARKET ST., LIMA, OH 45801 (NAICS 622110). OSHA activity number 341392991.
Where did this inspection happen?
- Establishment
- ST. RITA'S HEALTH PARTNERS
- Site address
- 730 W. MARKET ST.
- City
- LIMA
- State
- OH
- ZIP
- 45801
- Mailing
- 730 W. MARKET ST., LIMA, OH 45801
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 2518
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.137 C02 VIII
- Issued
- Abate by
- Penalty
- Initial $5000.00 · Current $2500.00 Reduced
8870
General-duty citation text
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-4 and Table I-5. a. St. Rita's Health Partners located in Lima, Ohio: On or about April 12, 2016, the employer did not ensure insulated gloves available for use by the electricians, were tested at six month intervals. Class I gloves #150-1200, assigned for use to an electrician, were last tested on September 1, 2015, and were due for inspection on March 1, 2016.
Recent events (2)
- — I (S) $2500
- — Z (S) $5000
1910.303 F01
- Issued
- Abate by
- Penalty
- Initial $3000.00 · Current $1500.00 Reduced
8870
General-duty citation text
29 CFR 1910.303(f)(1): Each disconnecting means required by this subpart for motors and appliances were not legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. a. St. Rita's Health Partners located in Lima, Ohio: On or about March 8, 2016, the employer did not ensure the breakers for the night lights in area 6K064 of the sixth floor renal telemetry department were marked to indicate their purpose.
Recent events (2)
- — I (S) $1500
- — Z (S) $3000
1910.333 A
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $3500.00 Reduced
8870
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices were not consistent with the nature and extent of the associated electrical hazards. a. St. Rita's Health Partners located in Lima, Ohio: On or about March 8, 2016, the employer did not ensure electrical safety-related work practices were used when an electrician was performing work on a lighting system located on the sixth floor of the hospital in the renal telemetry department. The electrician disconnected the energized conductors from the light ballast without first activating the breaker that was supplying power to the conductors. b. St. Rita's Health Partners located in Lima, Ohio: On or about March 8, 2016, the employer did not ensure electrical safety-related work practices were used when an electrician was performing work on a lighting system located on the sixth floor of the hospital in the renal telemetry department. A second electrician disconnected energized conductors housed in a junction box which supplied power to the lighting circuit without first activating the breaker that was supplying power to the conductors.
Recent events (2)
- — I (S) $3500
- — Z (S) $7000
1910.333 B02 II B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
8870
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on was not disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, were used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment were used as a substitute for lockout and tagging procedures. a. St. Rita's Health Partners located in Lima, Ohio: On or about March 8, 2016, the employer did not ensure an electrician disconnected electrical power from a lighting system located on the sixth floor of the hospital in the renal telemetry department, prior to performing work on the equipment. The electrician disconnected the energized conductors supplying power to the light ballast without first activating the breaker that was supplying power to the conductors. b. St. Rita's Health Partners located in Lima, Ohio: On or about March 8, 2016, the employer did not ensure an electrician disconnected electrical power from a lighting system located on the sixth floor of the hospital in the renal telemetry department, prior to performing work on the equipment. The second electrician disconnected energized conductors housed in a junction box which supplied power to the lighting circuit without first activating the breaker that was supplying power to the conductors.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 B01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
8870
General-duty citation text
29 CFR 1910.334(b)(1): Load rated switches, circuit breakers, or other devices specifically designed as disconnecting means were not used for the opening, reversing, or closing of circuits under load conditions. Cable connectors not of the load break type, fuses, terminal lugs, and cable splice connections may not be used for such purposes, except in an emergency. a. St. Rita's Health Partners located in Lima, Ohio: On or about March 8, 2016, the employer did not ensure the circuit breaker for the night lights located on the sixth floor of the hospital in the renal telemetry department, was opened to deenergize the lighting circuit. An employee disconnected the energized conductors to the light ballast by removing the wire nuts on the energized conductors as electrical power was being supplied to the light. b. St. Rita's Health Partners located in Lima, Ohio: On or about March 8, 2016, the employer did not ensure the circuit breaker for the night lights located on the sixth floor of the hospital in the renal telemetry department, was opened to deenergize the lighting circuit. An employee disconnected the energized conductors to the lighting circuit by removing the wire nuts on the conductors located in a junction box and then separating the conductors supplying power to the light.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 622110)
SAN JUAN, PR—2026-07-15
MUNICIPIO DE SAN JUAN
RIO PIEDRAS, PR—2026-07-15
CFSE
NORWALK, CA—2026-07-10
CPH HOSPITAL MANAGEMENT LLC
ANTIOCH, CA—2026-07-10
SUTTER DELTA MEDICAL CENTER
BURBANK, CA—2026-07-07
PROVIDENCE SAINT JOSEPH HOSPITAL
More inspections in OH
WELLINGTON, OH—2026-07-16
WHIRLAWAY CORPORATION
WAUSEON, OH—2026-07-16
WATSON WELL DRILLING INC.
SEVEN HILLS, OH—2026-07-15
STONEY ACRES BUILDERS LLC
SEVEN HILLS, OH—2026-07-15
GRB ENTERPRISES LLC
CHILLICOTHE, OH—2026-07-15
KENWORTH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341392991.