NIXON, TX —
OSHA Inspection: GUADALUPE VALLEY ELECTRIC COOPERATIVE, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of GUADALUPE VALLEY ELECTRIC COOPERATIVE, INC. in 2130 CR 127, NIXON, TX 78140 (NAICS 221122). OSHA activity number 341466332.
Where did this inspection happen?
- Establishment
- GUADALUPE VALLEY ELECTRIC COOPERATIVE, INC.
- Site address
- 2130 CR 127
- City
- NIXON
- State
- TX
- ZIP
- 78140
- Mailing
- 927 NORTH STATE HIGHWAY 46, SEGUIN, TX 78155
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 316
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.269 A02 I A
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.269(a)(2)(i)(A): Each employee was not trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments. On or about May 9, 2016 electricians were assigned to restore power to a water treatment plant. They conducted voltage checks on 480 volt transformers and one pad mounted transformer for which they had not been trained, exposing them to an arc flash hazard. The transformer was located at the Schertz-Seguin Local Government Corp, found near Nixon, TX
Recent events (2)
- — I (S) $0
- — Z (S) $7000
1910.269 A04 I
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.269(a)(4): Existing characteristics and conditions of electric lines and equipment that are related to the safety of the work to be performed were not determined before work on or near the lines or equipment was started. Such characteristics and conditions include, but are not limited to: (i) The nominal voltages of lines and equipment: On or about May 9, 2016 electricians were assigned to restore power to a water treatment plant. They were not informed of the nominal voltages they had to work with, exposing them to an arc flash hazard when testing a pad mounted transformer. The transformer was located at the Schertz-Seguin Local Government Corp, found near Nixon, TX
Recent events (2)
- — I (S) $0
- — Z (S) $7000
1910.269 C01 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.269(c)(1)(i): In assigning an employee or a group of employees to perform a job, the employer did not provide the employee in charge of the job with all available information that relates to the determination of existing characteristics and conditions required by paragraph (a)(4) of this section. On or about May 9, 2016 electricians were not provided with the voltage of the pad mounted transformer, exposing them to an arc flash hazard. The transformers were located at the Schertz-Seguin Local Government Corp. plant, found near Nixon, TX.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.269 C01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $7000.00
General-duty citation text
29 CFR 1910.269(c)(1)(ii): The employer did not ensure that the employee in charge conducts a job briefing that meets paragraphs (c)(2), (c)(3), and (c)(4) of this section with the employees involved before they start each job. On or about May 9, 2016 electricians did not conduct a job briefing before starting work, exposing them to an arc flash hazard while checking voltage on a pad mounted transformer. The transformers were located at the Schertz-Seguin Local Government Corp. plant, found near Nixon, TX.
Recent events (2)
- — I (S) $7000
- — Z (S) $0
1910.269 L03 I
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.269(l)(3)(i): The employer did not establish minimum approach distances not less than the distances computed by Table R-3 for ac systems or Table R-8 for dc systems. On or about May 9, 2016 electricians made contact with live electrical parts inside of a 2400 volt transformer vault and 480 volt transformers located inside of the plant, exposing them to an arc flash hazard. The transformers were located at the Schertz-Seguin Local Government Corp., found near Nixon, TX.
Recent events (2)
- — I (S) $0
- — Z (S) $7000
1910.269 L08 V
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
General-duty citation text
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2. On or about May 9, 2016, electricians were not wearing face shields, safety glasses, safety gloves, arc flash suits and using ear plugs while conducting a voltage checks on 480 volt and 2400 volt transformers, exposing them to an arc flash hazard. The transformers were located at the Schertz-Seguin Local Government Corp. plant, found near Nixon, TX.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.335 B01
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.335(b)(1): Safety signs, safety symbols, or accident prevention tags were not used where necessary to warn employees about electrical hazards which may endanger them as required by 29 CFR 1910.145. On or about May 9, 2016 a safety sign stating clearly the voltage of the secondary side was not provided for a 2400 volt transformer vault, exposing electricians to a arc flash hazard. The transformer was located at the Schertz-Seguin Local Government Corp., found near Nixon, TX.
Recent events (2)
- — I (S) $0
- — Z (S) $7000
More inspections in this industry (NAICS 221122)
LITTLETON, MA—2026-07-01
LITTLETON ELECTRIC LIGHT & WATER DEPARTMENT
PISCATAWAY, NJ—2026-06-30
PSE&G
BAYTOWN, TX—2026-06-30
CENTERPOINT ENERGY
SACRAMENTO, CA—2026-06-29
SACRAMENTO MUNICIPAL UTILITY DISTRICT
PHILADELPHIA, PA—2026-06-25
PECO ENERGY COMPANY
More inspections in TX
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.
FORT WORTH, TX—2026-07-10
RC PROFESSIONAL ROOFING OF TEXAS LLC
CYPRESS, TX—2026-07-10
FEDERICO CARVAJAL GARCIA
SAN ANTONIO, TX—2026-07-10
ED LONG'S METAL WORKS
SAN ANTONIO, TX—2026-07-09
WAREHOUSE RACK COMPANY, LP
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341466332.