Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DOMTAR LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of DOMTAR LLC in 200 N. GRAND AVE., ROTHSCHILD, WI 54474 (NAICS 322121). OSHA activity number 341544815.

Watch Domtar LLC — free Get an email when a new federal OSHA severe-injury report for Domtar LLC is published. One employer, no account, unsubscribe in one click.
Establishment
DOMTAR LLC
Site address
200 N. GRAND AVE.
City
ROTHSCHILD
State
WI
ZIP
54474
Mailing
200 N. GRAND AVE., ROTHSCHILD, WI 54474
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Case closed
Last modified
Data loaded
NAICS code
322121
Employees
416
Ownership type
A

3 citations on file for this inspection.

1910.269 A03 I C

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $7000.00
29 CFR 1910.269(a)(3)(i)(C): Before work begins, the host employer did not inform contract employers the information about the design and operation of the host employer's installation that the contract employer needs to make the assessment required by this section:  (a)  On or about May 24, 2016 in the Switch Yard; Domtar LLC did not provide relevant information on the Allis-Chalmers F-2 cubicle switchgear to include arc flash analysis information, 1-line diagrams, and wiring schematics to the contract employer prior to work commencing.  This exposed employees to electrical shock hazards.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7000

1910.269 L01 III

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $7000.00
29 CFR 1910.269(l)(1)(iii): Electric lines and equipment were not considered and treated as energized unless they had been deenergized in accordance with paragraph (d) or (m) of this section.  (a)  On or about May 24, 2016 in the Switch Yard; Domtar's employees were instructing the contract employees on work to be performed in close proximity of the lightning arresters.  The lightning arresters were not treated as energized exposing employees to electrical shock hazards.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7000

1910.332 B01

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  (a)  On or about May 24, 2016 in the Switch Yard; employees performing electrical activities near the Allis-Chalmers F-2 cubicle switchgear were not trained on the specific safety-related work practices, safety procedures, and other safety requirements.  This exposed employees to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

View DOMTAR LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341544815.