ROTHSCHILD, WI —
OSHA Inspection: DOMTAR LLC
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of DOMTAR LLC in 200 N. GRAND AVE., ROTHSCHILD, WI 54474 (NAICS 322121). OSHA activity number 341544815.
Where did this inspection happen?
- Establishment
- DOMTAR LLC
- Site address
- 200 N. GRAND AVE.
- City
- ROTHSCHILD
- State
- WI
- ZIP
- 54474
- Mailing
- 200 N. GRAND AVE., ROTHSCHILD, WI 54474
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 322121
- Employees
- 416
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.269 A03 I C
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
General-duty citation text
29 CFR 1910.269(a)(3)(i)(C): Before work begins, the host employer did not inform contract employers the information about the design and operation of the host employer's installation that the contract employer needs to make the assessment required by this section: (a) On or about May 24, 2016 in the Switch Yard; Domtar LLC did not provide relevant information on the Allis-Chalmers F-2 cubicle switchgear to include arc flash analysis information, 1-line diagrams, and wiring schematics to the contract employer prior to work commencing. This exposed employees to electrical shock hazards.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.269 L01 III
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
General-duty citation text
29 CFR 1910.269(l)(1)(iii): Electric lines and equipment were not considered and treated as energized unless they had been deenergized in accordance with paragraph (d) or (m) of this section. (a) On or about May 24, 2016 in the Switch Yard; Domtar's employees were instructing the contract employees on work to be performed in close proximity of the lightning arresters. The lightning arresters were not treated as energized exposing employees to electrical shock hazards.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.332 B01
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: (a) On or about May 24, 2016 in the Switch Yard; employees performing electrical activities near the Allis-Chalmers F-2 cubicle switchgear were not trained on the specific safety-related work practices, safety procedures, and other safety requirements. This exposed employees to electrical shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $7000
More inspections at DOMTAR LLC
CERRITOS, CA—2008-10-20 00:00:00
DOMTAR LLC
View DOMTAR LLC's full OSHA safety record →
More inspections in this industry (NAICS 322121)
CAMAS, WA—2026-07-07
WA317991935 - GEORGIA PACIFIC CONSUMER OPERATIONS LLC
MENASHA, WI—2026-06-17
ESSITY PROFESSIONAL HYGIENE NA LLC
SPRING GROVE, PA—2026-05-21
PIXELLE SPECIALTY SOLUTIONS LLC
VALLIANT, OK—2026-05-21
INTERNATIONAL PAPER COMPANY
GLENS FALLS, NY—2026-05-13
FINCH PAPER LLC
More inspections in WI
WAUSAU, WI—2026-07-16
MIRON CONSTRUCTION CO. INC.