MARIETTA, GA —
OSHA Inspection: PIEDMONT GRAPHICS, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PIEDMONT GRAPHICS, INC. in 1007 INDUSTRIAL PARK DRIVE, MARIETTA, GA 30062 (NAICS 323110). OSHA activity number 341553774.
Where did this inspection happen?
- Establishment
- PIEDMONT GRAPHICS, INC.
- Site address
- 1007 INDUSTRIAL PARK DRIVE
- City
- MARIETTA
- State
- GA
- ZIP
- 30062
- Mailing
- 1007 INDUSTRIAL PARK DRIVE, MARIETTA, GA 30062
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323110
- Employees
- 50
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.106 D04 I
- Issued
- Abate by
- Penalty
- Initial $6236.00 · Current $3741.00 Reduced
General-duty citation text
29 CFR 1910.106(d)(4)(i): "Construction." Inside storage rooms shall be constructed to meet the required fire-resistive rating for their use. Such construction shall comply with the test specifications set forth in Standard Methods of Fire Tests of Building Construction and Materials, NFPA 251-1969. Where an automatic sprinkler system is provided, the system shall be designed and installed in an acceptable manner. Openings to other rooms or buildings shall be provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height, or the floor in the storage area shall be at least 4 inches below the surrounding floor. Openings shall be provided with approved self-closing fire doors. The room shall be liquid-tight where the walls join the floor. A permissible alternate to the sill or ramp is an open-grated trench inside of the room which drains to a safe location. Where other portions of the building or other properties are exposed, windows shall be protected as set forth in the Standard for Fire Doors and Windows, NFPA No. 80-1968, which is incorporated by reference as specified in Sec. 1910.6, for Class E or F openings. Wood at least 1 inch nominal thickness may be used for shelving, racks, dunnage, scuffboards, floor overlay, and similar installations a) The facility - Employees are exposed to fire hazards in that METER X III liquid and Isopropyl Alcohol, both Category I flammable liquids are improperly stored.
Recent events (2)
- — I (S) $3741
- — Z (S) $6236
1910.106 D04 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.106(d)(4)(iii): Wiring. Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, shall be approved for general use. a) Employees are exposed to fire hazards in that, sufficient electrical switches and connectors are not provided in areas where METER X III liquid and Isopropyl Alcohol, both Category I flammable liquids are dispensed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 E06 II
- Issued
- Abate by
- Penalty
- Initial $8730.00 · Current $5235.00 Reduced
General-duty citation text
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected. a) Employees are exposed to fire hazards in that, a means of grounding and bonding are not provided where METER X III liquid and Isopropyl Alcohol, both Category I flammable liquids dispensed and transferred.
Recent events (2)
- — I (S) $5235
- — Z (S) $8730
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $3741.00 · Current $2244.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Near the Color Press - The employer exposed employees to fire hazards in that a relocatable power tap was connected (daisy chained) to a portable extension cord when providing power to a microwave and refrigerator.
Recent events (2)
- — I (S) $2244
- — Z (S) $3741
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Near the Color Press - Employees were exposed to fire hazards in that, a power strip and portable flexible cords were used to provide power to a microwave and a mini-fridge.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) Near the Color Press - Employees were exposed to fire hazards in that, materials and shelving restricted access to the power panel.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at PIEDMONT GRAPHICS, INC.
GREENSBORO, NC—2013-04-15 00:00:00
PIEDMONT GRAPHICS, INC
MARIETTA, GA—2012-08-02 00:00:00
PIEDMONT GRAPHICS, INC.
View PIEDMONT GRAPHICS, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 323110)
MINNEAPOLIS, MN—2026-05-20
111284 - MARTH GROUP LLC DBA ENPOINTE
GLENDALE, KY—2026-02-04
68801 - PG-GERALD LLC
PORTLAND, OR—2026-01-16
317742947 - PEP PRINTING INC
MINNEAPOLIS, MN—2025-11-18
110299 - OMEGA LITHOGRAPH INC
BELLINGHAM, WA—2025-09-05
WA317987718 - CAPITOL CITY PRESS INC
More inspections in GA
ROME, GA—2026-07-13
CAMP INDUSTRIES
SOUTH FULTON, GA—2026-07-10
REEDWICK, LLC
CONYERS, GA—2026-07-10
GOLDEN STATE FOODS
DALTON, GA—2026-07-10
ENGINEERED FLOORS, LLC
METTER, GA—2026-07-10
M.A.P.C CONSTRUCTION, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341553774.