Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,783,325Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DUNMORE RECREATION, LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of DUNMORE RECREATION, LLC in 200 TIGUE ST, DUNMORE, PA 18512 (NAICS 236220). OSHA activity number 342018280.

Watch Dunmore Recreation, LLC — free Get an email when a new federal OSHA severe-injury report for Dunmore Recreation, LLC is published. One employer, no account, unsubscribe in one click.
Site address
200 TIGUE ST
City
DUNMORE
State
PA
ZIP
18512
Mailing
200 TIGUE STREET, DUNMORE, PA 18512
Inspection type
Unprogrammed Related (G)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
6
Ownership type
A

7 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  a) First Floor Hall: A relocatable power tap, which is not intended for use on a construction, was installed and used in the hall outside the employer's offices to power a lamp and other devices, on or about January 10, 2017.  b) Old Boiler Room: A relocatable power tap, which is not intended for use on a construction, was installed and used as a multiple power outlet for the temporary electrical system, on or about January 10, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0

1926.404 B01 I

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites:  a) Dunmore, PA: The temporary electrical system installed by this employer's electrical subcontractor did not include ground fault circuit interrupters to protect workers from an electric shock hazard, on or about January 10, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0

1926.405 A02 II E

Serious Gravity 1 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(a)(2)(ii)(E): Lamps for general illumination were not protected from accidental contact or breakage:  a) Dunmore, PA: A pedestal lamp used by employees in a room where tools and equipment are stored was not equipped with a cover to protect the bulb from accidental contact or breakage, on or about January 10, 2017.  b) Dunmore, PA: A pedestal lamp used by employees to provide light in a hallway outside the company offices was not equipped with a cover to protect the bulb from accidental contact or breakage, on or about January 10, 2017.   ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0

1926.405 D

Serious Gravity 5 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front:  a) Dunmore, PA: Employees were exposed to an electric shock hazard while working in close proximity to a 200-amp panel box that was not equipped with a dead front or otherwise protected, on or out March 2, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0

1926.501 B01

Serious Gravity 5 2 instances 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.501(b)(1): Each employee on a walking/working surface with an unprotected side or edge which was 6 feet (1.8 m) or more above a lower level was not protected from falling by the use of guardrail systems, safety net systems, or personal fall arrest systems:  a) Dunmore, PA: Employees installing copper tubing in various location on the roof of a hotel structure that was 16 to 27 feet above the ground were not protected from falling, on or about January 10, 2017.  b) Dunmore, PA: Employees installing HVAC components traversed rooms using a balcony with an open side that was 8 feet above the ground and were not protected from falling, on or about January 10, 2017.  c) Dunmore, PA: Employees for an electrical subcontractor who installed Romex cable along the ceiling of the balconies, which was not equipped with guardrails, were exposed to a fall of 8 feet, on or about January 10, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0

1926.502 B01

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.502(b)(1): The top edge height of the top rails, or equivalent guardrail system members, was not 42 inches (1.1 m) plus or minus 3 inches (8 cm) above the walking/working level:  a) Third floor hallway: The walls along the hallway on the third floor were only 32 inches high, exposing workers to the potential for a fall of as much as 16 feet, on or about January 23, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0

1926.1053 B04

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.1053(b)(4): Ladders were used for purposes other than that which they were designed:  a) Dunmore, PA: Employees were exposed to a fall when a folded step ladder was improperly used to access the upper roof level, on or about January 10, 2017.  b) Dunmore, PA: Employees were exposed to a fall when a folded step ladder was improperly used to access the upper roof level, on or about January 26, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $0