Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: JW POWERLINE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of JW POWERLINE in 5697 TRANS PECOS RD., FORT STOCKTON, TX 79735 (NAICS 238210). OSHA activity number 342041621.

Watch JW Powerline — free Get an email when a new federal OSHA severe-injury report for JW Powerline is published. One employer, no account, unsubscribe in one click.
Establishment
JW POWERLINE
Site address
5697 TRANS PECOS RD.
City
FORT STOCKTON
State
TX
ZIP
79735
Mailing
700 S. FAIRGROUNDS RD., MIDLAND, TX 79701
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
135
Ownership type
A

5 citations on file for this inspection.

1910.269 A03 II A

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6926.00 · Current $4000.00 Reduced
29 CFR 1910.269(a)(3)(ii)(A): The contract employer did not ensure that each of its employees was instructed in the hazardous conditions relevant to the employee's work:    At the substation: On or about January 19, 2017, The contract employer did not ensure that each of its employees was instructed in the hazardous conditions relevant to the employee's work.  Employees were exposed to electrical shock hazards.
Recent events (3)
  • — F (S) $4000
  • — C (S) $6926
  • — Z (S) $6926

1910.333 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6926.00 · Current $4000.00 Reduced
29 CFR 1910.333(a)(1): The employer failed to ensure that live parts were de-energized before employees began to work on or near live parts.    At the substation: On or about January 19, 2017, at the substation; the employer did not ensure that live parts were de-energized before allowing employees to work on or near live parts.  Employees were exposed to electrical shock hazards.
Recent events (3)
  • — F (S) $4000
  • — C (S) $6926
  • — Z (S) $6926

1910.333 B02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6926.00 · Current $4000.00 Reduced
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives:    At the substation: On or about January 19, 2017, the employer did not provided OSHA rep with a written copy of the procedures as outlined in 29 CFR 1910.333(b)(2).
Recent events (3)
  • — F (S) $4000
  • — C (S) $6926
  • — Z (S) $6926

1910.333 B02 II B

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6926.00 · Current $4000.00 Reduced
29 CFR 1910.333(b)(2)(ii)(B): Control circuit devices, such as push buttons, selector switches, and interlocks, were used as the sole means for de-energizing circuits and equipment:    At the substation: On or about January 19, 2017, the employer relied on the use of a selector switch as thee sole means for de-energizing VISTA distribution switchgear.  The VISTA distribution switchgear was de-energized on the out-going side, but remained energized on the in-coming side.Employees were exposed to electrical hazards.
Recent events (3)
  • — F (S) $4000
  • — C (S) $6926
  • — Z (S) $6926

1910.333 B02 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6926.00 · Current $4000.00 Reduced
29 CFR 1910.333(b)(2)(iv): The employer did not properly verify if the components were positively de-energized or in an otherwise safe condition to protect the employees from an electrical shock hazard.     At the substation: On or about January 19, 2017, the employer did not verify equipment was positively de-energized.  Employees were exposed to electrical shock hazards.
Recent events (3)
  • — F (S) $4000
  • — C (S) $6926
  • — Z (S) $6926

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342041621.