Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: MEDTRONIC ANGIOLINK, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of MEDTRONIC ANGIOLINK, INC. in 37A CHERRY HILL DRIVE, DANVERS, MA 01923 (NAICS 339112). OSHA activity number 342152824.

Watch Medtronic Angiolink, INC. — free Get an email when a new federal OSHA severe-injury report for Medtronic Angiolink, INC. is published. One employer, no account, unsubscribe in one click.
Site address
37A CHERRY HILL DRIVE
City
DANVERS
State
MA
ZIP
01923
Mailing
37A CHERRY HILL DRIVE, DANVERS, MA 01923
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
339112
Employees
600
Ownership type
A

4 citations on file for this inspection.

1910.303 F02

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $4889.00 · Current $3000.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    (a) Location - 37A Cherry Hill Drive, Danvers, MA:  On or about 3/7/17, the employer failed to ensure the panel was correctly labeled on a service feeder they were working on.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4889

1910.333 A02

Serious Gravity 10 1 instance 2 exposed
Issued
Penalty
Initial $11408.00 · Current $6500.00 Reduced
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved:    (a) Location - 37A Cherry Hill Drive, Danvers, MA:  On or about 3/4/17, the employer failed to ensure that safety related work practices (consistent with the nature and extent of the associated electrical hazard) were used by employees while they were working on energized electric.
Recent events (2)
  • — I (S) $6500
  • — Z (S) $11408

1910.333 B02

Serious Gravity 10 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2):  (a) Location - 451 Boston Road, Billerica, MA: On or about 12/9/16, the employer failed to ensure employees were locking or tagging energized electrical circuits. The employer failed to ensure employees were protected from energized electrical parts while replacing lighting ballast.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 II

Other-than-serious 1 instance 2 exposed
Issued
Penalty
Initial $686.00 · Current $500.00 Reduced
29 CFR 1910.335(a)(1)(ii): Protective equipment was not maintained in a safe, reliable condition and/or was not periodically inspected or tested:    (a) Location - 37A Cherry Hill Drive, Danvers, MA:  On or about 3/7/17, the employer failed to ensure that the insulated gloves employees were using were inspected.
Recent events (2)
  • — I (O) $500
  • — Z (O) $686

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342152824.