Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: LOWE'S PA RDC 961

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of LOWE'S PA RDC 961 in 1201 KEYSTONE BOULEVARD, POTTSVILLE, PA 17901 (NAICS 493110). OSHA activity number 342209970.

Watch Lowe'S PA RDC 961 — free Get an email when a new federal OSHA severe-injury report for Lowe'S PA RDC 961 is published. One employer, no account, unsubscribe in one click.
Establishment
LOWE'S PA RDC 961
Site address
1201 KEYSTONE BOULEVARD
City
POTTSVILLE
State
PA
ZIP
17901
Mailing
1201 KEYSTONE BOULEVARD, POTTSVILLE, PA 17901
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
725
Ownership type
A

6 citations on file for this inspection.

1910.178 G01

Serious Gravity 1 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $4617.00 · Current $3464.00 Reduced
29 CFR 1910.178(g)(1): Battery charging installations were not located in areas designated for that purpose.    a) Old battery charging room, the room was used to store combustible items not related to the charging operations such as empty cardboard boxes, plastic trays, painting supplies including rags, on or about, March 29, 2017.    b) New battery charging room, the room was used to store plastic PPE including aprons and face shields, and containers used for maintenance tasks which contain cardboard and other combustible materials, on or about March 29, 2017.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $3464
  • — Z (S) $4617

1910.22 A01

Serious Gravity 1 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, service rooms, and walking-working surfaces were not kept in a clean, orderly, and sanitary condition.  a) Old battery charging room, the room was used to store combustible items not related to the charging operations such as empty cardboard boxes, plastic trays, painting supplies including rags, on or about, March 29, 2017.  b) New battery charging room, the room was used to store plastic PPE including aprons and face shields, and containers used for maintenance tasks which contain cardboard and other combustible materials, on or about March 29, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 I A

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $4617.00 · Current $3462.00 Reduced
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910.    a) Old battery charging room,  materials including high pressure washers, and a wooden crate were stored approximately one foot in front of breaker panels and switch gear which were at or above 120 VAC, and the clear space directly in front of the cabinets was less than 36 inches, on or about, March 29, 2017.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $3462
  • — Z (S) $4617

1910.37 A03

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $4617.00 · Current $3462.00 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    a) Old battery charging room, the west side egress aisle to exit was partially blocked with cardboard boxes and sheet metal pieces, on or about, March 29, 2017.    b) Old battery charging room,  the east side egress aisle to exit was partially blocked with a metal storage rack, and cardboard boxes on the floor, on or about, March 29, 2017.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $3462
  • — Z (S) $4617

1910.37 B04

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:    a) Old battery charging room, the east and west side egress aisles to exit were not posted with signage indicating that they were the routes to exit, on or about, March 29, 2017.    b) New battery charging room, the east and west side egress aisles to exit were not posted with signage indicating that they were the routes to exit, on or about, March 29, 2017.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.1200 F06 I

Other-than-serious 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00

Hazardous substances P135S111

29 CFR 1910.1200(f)(6)(i): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the information required by 29 CFR 1910.1200(f)(1)(i) through 29 CFR 1910.1200(f)(1)(v)  a) New battery charging room, a garden sprayer which was used to spray ProWash Clear neutralizer, contained potassium carbonate and sodium carbonate and was not labeled with its contents, on or about, March 29, 2017.  b) Old battery charging room,  three garden sprayers which were used to spray ProWash Clear neutralizer contained potassium carbonate and sodium carbonate and were not labeled with their contents, on or about, March 29, 2017.  ABATEMENT CERTIFICATION REQUIRED