OSHA Inspection: DARIUSZ MROCZEK

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DARIUSZ MROCZEK in 36 WEST 93RD ST, NEW YORK, NY 10025 (NAICS 238990). OSHA activity number 342218674.

Watch Dariusz Mroczek — free Get an email when a new federal OSHA severe-injury report for Dariusz Mroczek is published. One employer, no account, unsubscribe in one click.
Establishment
DARIUSZ MROCZEK
Site address
36 WEST 93RD ST
City
NEW YORK
State
NY
ZIP
10025
Mailing
59-72 61ST STREET, MASPETH, NY 11378
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238990
Employees
2
Ownership type
A

6 citations on file for this inspection.

1926.403 B02

Serious Gravity 1 1 instance 9 exposed
Issued
Penalty
Initial $1630.00 · Current $1141.00 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) Boiler Room - On or prior to March 30, 2017, employees were exposed to electrical hazards due to the use of the welding power cord and other power cords not used in accordance with instructions including, but not limited to, not providing Ground-Fault Protection for employees using equipment plugged into the power cords and the flexible power cords were not protected from accidental damage or installed properly.  The welding power cord and other power cords were directly connected to 30 Amp breakers in the 208Y/120V 3PH 4W electrical panel with its cover removed.
Recent events (2)
  • — I (S) $1141
  • — Z (S) $1630

1926.403 I02 I

Serious Gravity 1 1 instance 9 exposed
Issued
Penalty
Initial $1630.00 · Current $1141.00 Reduced
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph:    a) Boiler Room - On or prior to March 30, 2017, employees were exposed to electrical hazards due to a 208Y/120V 3PH 4W electrical panel had its cover removed.
Recent events (2)
  • — I (S) $1141
  • — Z (S) $1630

1926.404 B01 II

Serious Gravity 1 1 instance 9 exposed
Issued
Penalty
Initial $1630.00 · Current $1141.00 Reduced
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection:    a) Boiler Room - On or prior to March 30, 2017, employees were exposed to electrical hazards due to the welding power cord outlet and the other power cord outlets directly connected to 30 Amp breakers in the 208Y/120V 3PH 4W electrical panel with its cover removed did not have approved ground fault circuit interrupters (GFCIs) for personal protection.
Recent events (2)
  • — I (S) $1141
  • — Z (S) $1630

1926.405 A02 I

Serious Gravity 1 1 instance 9 exposed
Issued
Penalty
Initial $1630.00 · Current $1141.00 Reduced
29 CFR 1926.405(a)(2)(i): Temporary wiring was not removed immediately upon completion of construction or the purpose for which the wiring was installed:    a) Boiler Room - On or prior to March 30, 2017 employees were exposed to electrical hazards due to temporary wiring used for welding not being removed immediately upon completion of the welding.  A temporary welding power cord and other power cords were directly connected to 30 Amp breakers in the 208Y/120V 3PH 4W electrical panel.
Recent events (2)
  • — I (S) $1140.96
  • — Z (S) $1630

1926.405 A02 II I

Serious Gravity 1 1 instance 9 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(a)(2)(ii)(I): Flexible cords and cables used for temporary wiring were not protected from damage:  a) Boiler Room - On or prior to March 30, 2017, employees were exposed to electrical hazards due to the temporary welding power cord and other power cords that were directly connected to 30 Amp breakers in the 208Y/120V 3PH 4W electrical panel not being protected from damage.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 G02 IV

Serious Gravity 1 1 instance 9 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws:  a) Boiler Room - On or prior to March 30, 2017, employees were exposed to electrical hazards due to the welding power cord and the other power cords directly connected to 30 Amp breakers in the 208Y/120V 3PH 4W electrical panel with its cover removed were not provided with strain relief.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342218674.