YOUNGSTOWN, OH —
OSHA Inspection: JENKINS SIGN COMPANY INC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of JENKINS SIGN COMPANY INC in 1400 MAHONING AVE, YOUNGSTOWN, OH 44509 (NAICS 339950). OSHA activity number 342295888.
Where did this inspection happen?
- Establishment
- JENKINS SIGN COMPANY INC
- Site address
- 1400 MAHONING AVE
- City
- YOUNGSTOWN
- State
- OH
- ZIP
- 44509
- Mailing
- 1400 MAHONING AVE, YOUNGSTOWN, OH 44509
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 339950
- Employees
- 14
- Ownership type
- A
Citations
13 citations on file for this inspection.
1910.107 B02
- Issued
- Abate by
- Penalty
- Initial $2897.00 · Current $1449.00 Reduced
General-duty citation text
29 CFR 1910.107(b)(2): The interior surface of spray booth(s) were not smooth and continuous without edges and otherwise designed to prevent pocketing of residues and to facilitate cleaning and washing without injury: On or about May 3, 2017, the employer failed to ensure that the paint booth's interior had smooth and continuous edges free from pocketed residue. Tools, cleaning equipment, paint and flammable materials were stored in the paint booth during operation, including but not limited to, a permanently placed fire extinguisher, a fan, and tool boxes.
Recent events (2)
- — I (S) $1448.5
- — Z (S) $2897
1910.107 B05 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.107(b)(5)(iv): Space within the spray booth on the downstream and upstream sides of filters were not protected with approved automatic sprinklers: On or about May 3, 2016,the paint booth did not have a sprinkler system. Employees paint with category 3 flammable liquids.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.107 C06
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: On or about May 3, 2016, the employer exposed employees to injuries from explosion and fire hazards; the lighting in the spray booth is not rated for use in paint booth operations. Paint booths should have class 1 electrical; the paint booth has lighting that is only UL rated for damp conditions, not explosive conditions. In the paint booth two (4) light fixtures are not rated for use in class 1 conditions.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $2173.00 · Current $1087.00 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. a. On or about May 3, 2017, the circuit breakers in the shear area were not labeled, exposing employees to an arc flash. b. On or about May 3, 2017, the circuit breakers by the Multicam MG router were not labeled, exposing employees to an arc flash.
Recent events (2)
- — I (S) $1086.5
- — Z (S) $2173
1910.303 G01 I
- Issued
- Abate by
- Penalty
- Initial $2173.00 · Current $1087.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: On or about May 3, 2017, the circuit breaker panel that was located at the shear area did not have at least 3 feet of access and working space in front of the panels, exposing employees to an arc flash hazard.
Recent events (2)
- — I (S) $1086.5
- — Z (S) $2173
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $2173.00 · Current $1087.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): On or about May 3, 2017, the 480 volt panel box was missing blanks for the circuits, that was located by the Multicam MG router, thus exposing employees to live electrical parts.
Recent events (2)
- — I (S) $1086.5
- — Z (S) $2173
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $2173.00 · Current $1087.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about May 3, 2017, a receptacle was missing the face plate cover on the wall in the plastics department, exposing employees to live electrical currents.
Recent events (2)
- — I (S) $1086.5
- — Z (S) $2173
1910.305 C04
- Issued
- Abate by
- Penalty
- Initial $2173.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes shall have faceplates installed so as to completely cover the opening and seat against the finished surface. On or about May 3, 2017, the snap switches located in the plastics department were missing the faceplate, thus exposing employees to live electrical currents.
Recent events (2)
- — I (S) $0
- — Z (S) $2173
1910.1200 H01
- Issued
- Abate by
- Penalty
- Initial $2173.00 · Current $1087.00 Reduced
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: On or about May 3, 2017, the employer failed to train employees on the safe use and handling of hazardous chemicals used in the workplace. Employees work with or are exposed to hazardous chemicals containing xylene, ethylbenzene, and n-butyl acetate which can be absorbed through contact with the skin.
Recent events (2)
- — I (S) $1086.5
- — Z (S) $2173
1910.1200 E01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: On or about May 3, 2017, the employer failed to develop or implement a written hazard communication program at the facility. Employees work with or are exposed to various paints including but not limited to Grip Guard Basecoat MM 671 Blue (Green) Transparent, Grip-Guard Basecoat MM 110 White, and Grip-Guard Basecoat MM140 Deep Black that are used for painting signs.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 C02 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.134(c)(2)(ii): The employer did not establish and implement those elements of a written program necessary to ensure that any employee using a respirator voluntarily was medically able to use that respirator, and that the respirator was cleaned, stored, and maintained so that its use does not present a health hazard to the user: a. On or before May 3, 2017, the employer did not establish and implement a written respiratory protection program which included a medical evaluation and ensuring that the respirator is cleaned, stored, and maintained, for the voluntary use of respirators.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.134 K06
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.134(k)(6): The employer did not provide the basic advisory information on respirators, as presented in Appendix D of 29 CFR 1910.134, in written or oral format to employees who wear respirators when such use was not required by the employer: a. On or before May 3, 2017, the employer did not ensure that employees voluntarily using the 3M Half Mask respirator, were provided with Appendix D of 29 CFR 1910.134.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.179 J02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.179(j)(2): The following items were not be inspected for defects at intervals as defined in paragraph (j)(1)(ii) of this section or as specifically indicated, including observation during operation for any defects which might appear between regular inspections: On or about May 22, 2017, the employer failed to ensure that monthly inspections were being performed on the cranes, including but not limited to the Radocy Inc. 2000 pound 65' Saturn II 1985 (S/N 062865) and the Radocy Inc. 2000 pound 65' Saturn II 1997 (062497). The last inspection was performed May 15, 2014.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at JENKINS SIGN COMPANY INC
YOUNGSTOWN, OH—1989-08-08 00:00:00
JENKINS SIGN COMPANY, INC.
View JENKINS SIGN COMPANY INC's full OSHA safety record →
More inspections in this industry (NAICS 339950)
APEX, NC—2026-07-07
161498 - SEVEN SPRINGS, INC.
MINNEAPOLIS, MN—2026-06-30
111500 - SIGNMINDS INC
ANGIER, NC—2026-06-29
161462 - CAROLINA SIGN AND SERVICE, LLC
GREENE, NY—2026-06-17
RAPP SIGNS, INC.
LEXINGTON, KY—2026-06-11
69225 - INTEGRATED SIGN - GRAPHIC INC
More inspections in OH
WELLINGTON, OH—2026-07-16
WHIRLAWAY CORPORATION
WAUSEON, OH—2026-07-16
WATSON WELL DRILLING INC.
SEVEN HILLS, OH—2026-07-15
STONEY ACRES BUILDERS LLC
SEVEN HILLS, OH—2026-07-15
GRB ENTERPRISES LLC
CHILLICOTHE, OH—2026-07-15
KENWORTH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342295888.